2015-06-08 12:59:17 | 1ST REVIEW: FBC 2010 MECHANICAL |
| |
| 1) SHEET M1.1: THE FLOOR PLAN LAYOUT AND ROOM |
| CONFIGURATIONS ON THIS PLAN SHEET DO NOT MATCH THE |
| LAYOUTS SHOWN ON THE OTHER PLAN SHEETS IN THE SET. |
| PLEASE REVIEW AND REVISE. |
| 2) M1.1: THE LOAD ASSUMPTIONS DO NOT INDICATE ANY |
| BTU/HR'S FOR THE FREEZER AND REFRIGERATOR, HOWEVER THE |
| SUBMITTED SYSTEM SIZING CALCS INDICATE LOAD VALUES FOR |
| EACH. |
| 3) M1.1: THE GENERATOR (#15 IN THE SCHEDULE) , IS |
| MIS-LABELED (#14 HANDSINK). PLEASE NOTE THAT COMPLETE |
| PLANS AND DETAILS SHALL BE PROVIDED FOR THE GENERATOR |
| UNDER SEPARATE PERMIT. |
| 4) PROVIDE HOOD PLANS AND SPECIFICATIONS INCLUDING |
| DIMENSIONED FRONT AND PLAN VIEW DRAWINGS, HOOD AND |
| EXHAUST DUCT SIZES, DUCT RUN, TERMINATION LOCATION, AND |
| EQUIPMENT SCHEDULE FOR THE EXHAUST FAN - SEE SECTION |
| 507 FBC-10 MECHANICAL. SUBMIT A VALID PRODUCT APPROVAL |
| OR MIAMI DADE NOA FOR ROOF-MOUNTED FAN. |
| 5) M1,1: EQUIPMENT ID. #4 IS INDICATING A GAS STOVE, |
| HOWEVER #4 IS INDICATING A KETTLE ON THE ARCHITECTURAL |
| AND PLUMBING SHEETS: PLEASE CLARIFY. |
| 6) P.01: THE CONDENSATE FROM THE FREEZER AND COOLER |
| SHALL NOT DRAIN INTO THE SANITARY SEWER- SECTION 90-126 |
| CITY OF WEST PALM BEACH CODE OF ORDINANCES. PLEASE |
| CHOOSE ANOTHER LOCATION THAT IS IN COMPLIANCE WITH |
| SECTION 307. |
| 7) PROVIDE COMPLETE REFRIGERATION PLANS AND |
| SPECIFICATIONS FOR THE NEW COOLER AND FREEZER INCLUDING |
| A) SYSTEM SIZING CALCULATIONS B) EQUIPMENT SCHEDULES- |
| MAKES, MODELS, CAPACITIES OF CONDENSERS AND EVAPORATORS |
| C) EQUIPMENT LOCATIONS AND INSTALLATION DETAILS D) |
| PIPING RUNS AND SPECIFICATIONS, PIPE INSULATIONS ETC. |
| E) WALK-IN WALLS, FLOORS, AND CEILINGS CONSTRUCTION |
| DETAILS INCLUDING INSULATION THICKNESS AND TYPE. |
| 8) PROVIDE WIND LOAD TIE DOWN ENGINEERING FOR THE RTU'S |
| AND CURBS, AND FOR THE WALK-IN BOX CONDENSERS. PLEASE |
| INCLUDE TWO COPIES OF VALID FL. PRODUCT APPRIOVALS OR |
| MIAMI-DADE NOA'S FOR CONDENSER STANDS AND CURBS. |
| 9) SUBMIT PRODUCT DATA OR CUT SHEETS FOR ALL EQUIPMENT |
| SPECIFIED IN THE SCHEDULE |
| |
| |
| |
| CHRISTOPHER COLE |
| MECHANICAL PLANS EXAMINER |