2015-05-27 15:09:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) PROVIDE HAZARD CLASSIFICATION FOR EACH AREA PER NFPA
 101.
  
 2) PROVIDE A LIFE SAFETY PLAN. COMPLETE LIFE SAFETY
 PLANS SHALL BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS,
 TRAVEL DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END
 CORRIDORS, EXIT SIGNS, EMERGENCY LIGHTING, EXITS
 LEADING TO A PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS,
 AND ALL FIRE SAFETY FEATURES AND EQUIPMENT.
  
 3) SHEET A.01 INDICATES "NO" FRIE SPRINKLER. SHEET A.03
 INDICATES "YES" FIRE SPRINKLER. PLEASE INDICATE WHICH
 IS CORRECT. FIRE SPRINKLER AND FIRE ALARM SHALL BE DONE
 UNDER SEAPRATE SHOP DRAWINGS.
  
 4) BASED ON NO SPRINKLER PROTECTION A SECOND EXIT MAYBE
 REQUIRED IN THE FREEZER. SPRINKLER PROTECTION SHALL BE
 EXTENDED TO THE COOLER AND FREEZER.
  
 5) IT IS RECOMMENDED NOT TO LOSE ACCESS TO THE REAR
 DOORS AS THEY CAN BE USED AS ALTERNATE EXITS. CONSIDER
 CREATING HALLWAY ACCESS TO THE AT LEAST ONE REAR DOOR.
 IF A SECOND EXIT IS REQUIRED FROM THE FREEZER CREATE
 ACCESS HALLWYA TO BOTH REAR EXITS. SHOULD DOORS NOT BE
 USED, SIGNS ON EXTERIOR OF DOOR INDICATING 'NO ACCESS"
 ON EACH.
  
 6) ADD EXIT SIGN AT THE INSIDE LARGE AREA AT FRONT
 FOYER DOOR .
  
 7) ADD EXIT SIGN INSIDE THE FREEZER FOR EACH EXIT DOOR.
  
 8) ADD EMERGENCY LIGHTING INSIDE THE FEEZER.
  
 9) ADD EXIT LIGHT INSIDE THE COOLER.
  
 10) ADD EMERGENCY LIGHTING INSIDE THE COOLER.