2015-05-27 15:09:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) PROVIDE HAZARD CLASSIFICATION FOR EACH AREA PER NFPA |
| 101. |
| |
| 2) PROVIDE A LIFE SAFETY PLAN. COMPLETE LIFE SAFETY |
| PLANS SHALL BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, |
| TRAVEL DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END |
| CORRIDORS, EXIT SIGNS, EMERGENCY LIGHTING, EXITS |
| LEADING TO A PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, |
| AND ALL FIRE SAFETY FEATURES AND EQUIPMENT. |
| |
| 3) SHEET A.01 INDICATES "NO" FRIE SPRINKLER. SHEET A.03 |
| INDICATES "YES" FIRE SPRINKLER. PLEASE INDICATE WHICH |
| IS CORRECT. FIRE SPRINKLER AND FIRE ALARM SHALL BE DONE |
| UNDER SEAPRATE SHOP DRAWINGS. |
| |
| 4) BASED ON NO SPRINKLER PROTECTION A SECOND EXIT MAYBE |
| REQUIRED IN THE FREEZER. SPRINKLER PROTECTION SHALL BE |
| EXTENDED TO THE COOLER AND FREEZER. |
| |
| 5) IT IS RECOMMENDED NOT TO LOSE ACCESS TO THE REAR |
| DOORS AS THEY CAN BE USED AS ALTERNATE EXITS. CONSIDER |
| CREATING HALLWAY ACCESS TO THE AT LEAST ONE REAR DOOR. |
| IF A SECOND EXIT IS REQUIRED FROM THE FREEZER CREATE |
| ACCESS HALLWYA TO BOTH REAR EXITS. SHOULD DOORS NOT BE |
| USED, SIGNS ON EXTERIOR OF DOOR INDICATING 'NO ACCESS" |
| ON EACH. |
| |
| 6) ADD EXIT SIGN AT THE INSIDE LARGE AREA AT FRONT |
| FOYER DOOR . |
| |
| 7) ADD EXIT SIGN INSIDE THE FREEZER FOR EACH EXIT DOOR. |
| |
| 8) ADD EMERGENCY LIGHTING INSIDE THE FEEZER. |
| |
| 9) ADD EXIT LIGHT INSIDE THE COOLER. |
| |
| 10) ADD EMERGENCY LIGHTING INSIDE THE COOLER. |