2015-06-16 14:40:23PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 1. AS PER NEC 110.16, PANELS SHALL BE MARKED WITH THE
 REQUIRED ARC-FLASH PROTECTION WARNING LABEL.
 2. AS PER NEC 210.8(B)(5), ALL 125 V, 15 ? 20 AMP
 OUTLETS WITHIN 6? OF A SINK SHALL BE GFI PROTECTED.
 3. AS PER NEC 230.8, ALL UNDERGROUND SERVICE RACEWAYS
 SHALL BE SEALED TO AVOID MOISTURE ETC. AS PER NEC
 300.5.
 4. AS PER NEC 230.95, THREE PHASE WYE SERVICES OF 1000
 AMPS OR GREATER REQUIRE GFI PROTECTION.
 5. AS PER NEC 300.7, RACEWAYS EXPOSED TO DIFFERENT
 TEMPERATURES ENVIRONMENTS SHALL BE SEALED TO AVOID THE
 TRANSFER WARM AIR INTO THE COLD SPACE,
 6. AS PER NEC 422.52, ELECTRIC WATER COOLERS SHALL BE
 GFI PROTECTED.
 7. AS PER NEC 700.12, YOU SHALL INDICATE THE CIRCUIT
 NUMBER SERVING EACH EMERGENCY LIGHT TO ASCERTAIN
 COMPLIANCE IN THAT THEY HAVE TO BE ON THE SAME LIGHTING
 CIRCUIT AS THE AREA THEY OCCUPY.
 8. AS PER NEC 760.4, THE CIRCUIT SUPPLYING THE FACP
 SHALL BE LABELED AND IDENTIFIED ACCORDINGLY.
 9. FBC-ENERGY CONSERVATION, AMONG OTHER REQUIREMENTS,
 ALL LIGHTING SHALL COMPLY WITH SECTION 505 OF THIS
 CODE.
  
 IF YOU HAVE ANY QUESTIONS, OR I CAN BE OF FURTHER
 ASSISTANCE, PLEASE DO NOT HESITATE TO CONTACT ME.
  