2015-06-16 14:40:23 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| THE CORRECTIONS NOTED. |
| |
| THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| RESUBMITTED FOR A SECOND REVIEW: |
| |
| 1. AS PER NEC 110.16, PANELS SHALL BE MARKED WITH THE |
| REQUIRED ARC-FLASH PROTECTION WARNING LABEL. |
| 2. AS PER NEC 210.8(B)(5), ALL 125 V, 15 ? 20 AMP |
| OUTLETS WITHIN 6? OF A SINK SHALL BE GFI PROTECTED. |
| 3. AS PER NEC 230.8, ALL UNDERGROUND SERVICE RACEWAYS |
| SHALL BE SEALED TO AVOID MOISTURE ETC. AS PER NEC |
| 300.5. |
| 4. AS PER NEC 230.95, THREE PHASE WYE SERVICES OF 1000 |
| AMPS OR GREATER REQUIRE GFI PROTECTION. |
| 5. AS PER NEC 300.7, RACEWAYS EXPOSED TO DIFFERENT |
| TEMPERATURES ENVIRONMENTS SHALL BE SEALED TO AVOID THE |
| TRANSFER WARM AIR INTO THE COLD SPACE, |
| 6. AS PER NEC 422.52, ELECTRIC WATER COOLERS SHALL BE |
| GFI PROTECTED. |
| 7. AS PER NEC 700.12, YOU SHALL INDICATE THE CIRCUIT |
| NUMBER SERVING EACH EMERGENCY LIGHT TO ASCERTAIN |
| COMPLIANCE IN THAT THEY HAVE TO BE ON THE SAME LIGHTING |
| CIRCUIT AS THE AREA THEY OCCUPY. |
| 8. AS PER NEC 760.4, THE CIRCUIT SUPPLYING THE FACP |
| SHALL BE LABELED AND IDENTIFIED ACCORDINGLY. |
| 9. FBC-ENERGY CONSERVATION, AMONG OTHER REQUIREMENTS, |
| ALL LIGHTING SHALL COMPLY WITH SECTION 505 OF THIS |
| CODE. |
| |
| IF YOU HAVE ANY QUESTIONS, OR I CAN BE OF FURTHER |
| ASSISTANCE, PLEASE DO NOT HESITATE TO CONTACT ME. |
| |