2015-06-08 09:59:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050842
 ADD: 1100 W TECHNOLOGY PLACE # 104
 CONT: HEDRICK BROS.
 TEL: (561)689-8880
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 08/2015
 ACTION: DENIED
  
 1)SHEET A.01 THE PROJECT DATA INDICATES THE OCCUPANCY
 AS A F1 OCCUPANCY. WHERE THE PLANS INDICATE A MIXED USE
 OCCUPANCY BETWEEN A F-1 AND STORAGE OCCUPANCY AND
 OFFICE AS A ACCESSORY OCCUPANCY. WHERE LESS THAN 10% OF
 THE FLOOR AREA OF THE BUILDING IS USED IN A OCCUPANCY
 TYPE IT IS CONSIDERED A ACCESSORY OCCUPANCY. OVER 10 %
 OF THE BUILING FLOOR AREA IT IS CONSIDERED A MIXED USE
 BUILDING. THE QUESTION IS IF THE STORAGE OCCUPANCY IS
 TO BE CONSIDERED A S1 OR S2. THE S2 OCCUPANCY DOES
 INCLUDE FROZEN FOODS, FOOD PRODUCT AND THIS IS THE
 QUESTION, DAIRY PRODUCTS IN NONWAXED COATED PAPER
 CONTAINERS? HOW IS THE ICE CREAM PACKAGED?
  
 2) TABLE 508.4 DOES NOT REQUIRE OCCUPANCY SEPARATION
 BETWEEN THE F1 & S1 WHEREAS THE F1 & S2 DOES REQUIRE
 SEPARATION, 2 HR IF NON-SPRINKLERED & 1 HOUR FOR
 SPRINKLERED. THE OTHER OPTION IS TO REVIEW THE
 REQUIREMENTS OF NON-SEPARATED OCCUPANCIES FOUND UNDER
 FBC-B 508.3.
  
 3) THE OCCUPANCY COUNT IS TAKEN ON THE WHOLE OF THE
 FACILITY BEING F1 AND THE OCCUPANT LOAD TAKEN AT 100
 SQ. FT/ PER OCCUPANT. STORAGE STOCK AND SHIPPING ARE TO
 BE TAKEN AT 300 GROSS AND BUSINESS AT 100 GROSS. PLEASE
 REVISE THE OCCUPANCY COUNT. 2010 FBC-B TABLE 1004.1.1.
  
 4) THE COVERSHEET INDICATES THIS BUILDING NOT FIRE
 SPRINKLERED AND ADDS THE STATEMENT EXIT TRAVEL 200 FT.
 W/O FIRE SPRINKLERS. SHEET A.03 STATES THE BUILDING IS
 FIRE SPRINKLERED BUT THE TRAVEL DISTANCE IS STILL AT
 200 FT, TAKEN FOR F1 NON-FIRE SPRINKLERED? SEE FBC-B
 TABLE 1016.1.
  
 5) THE SHEET A.03 SHOWS (2) NEW COOLER AND FREEZERS
 COMBINED THEY ARE WELL OVER 400 SQ. FT. IN AREA. FBC-B
 2603.4.1.3 IN NON-SPRINKLERED BUILDINGS LIMITS THE AREA
 TO A AGGREGATE AREA OF 400 SQ. FT.
  
 6A) THE WALK IN CCOLER & FREEZERS ARE TO BE UNDER
 SEPARATE PERMIT WITH ASSOCIATED FEES. THEY WILL NEED TO
 SHOW COMPLIANCE WITH 2603.4.1.2 (1-4). THEY WILL ALSO
 NEED TO SUPPLY FRAMING SPANS FOR THE WALLS & CEILING,
 SHOW ALLOWABLE DEFLECTION LIMITS FBC-B TABLE 1604.3.
  
 6B) THE FREEZER APPEARS IT MAY BE LARGER THAN 1000 SQ,
 FT. IF SO IT WILL NEED TO COMPLY WITH 1015.5 ALSO SEE
 EXCEPTION. PLEASE ALSO NOTE THAT FOR UNSPRINKLERED
 BUILDINGS COMMON PATH OF TRAVEL IS LIMITED TO 50 FT.
 FOR F & S OCCUPANCIES. SEE FBC-B 1014.3 EXCEPTION # 7.
  
 7) SHEET M-5 SHOWS DETAILS FOR THE ROOF TOP A/H UNITS
 ON CURBS. NOTE THERE ARE NO STRUCTURAL SHEETS SHOWING
 THE NEW HOLES CUT INTO THE ROOF DECK, NOR IS THERE
 INFORMATION IF THE EXISTING FRAMING SYSTEM WILL TAKE ON
 THE ADDITIONAL POINT LOADING OR CONCENTRATED LOADS
 WITHOUT ANY REINFORCEMENT? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. FBC-B 1607.4. / 1607.11.1
 DISTRIBUTION OF ROOF LOADS.
  
 8A) SHEET M5 SHOWS A DETAIL OF A NEW ROOF CURB BUT
 THERE IS NO INFORMATION ON THE ATTACHMENT TO THE ROOF
 FRAMING SYSTEM PART OF COMPONENTS & CLADDING, WILL NEED
 TO SUBMIT PRODUCT APPROVAL FOR CURB. 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS, ROOF TOP CURBS
  
 8B) THE OTHER ISSUE THIS SAME DETAIL INDICATES SEE THE
 PRODUCT APPROVALS FOR THE ATTACHMENT OF THE AIR HANDLER
 TO THE ROOFTOP CURB. THIS IS NOT PART OF A PRODUCT
 APPROVAL AND WILL NEED TO BE ENGINEERED TO THE SITE
 SPECIFIC JOBSITE CONDITIONS. SEE 2010 FBC-B 1609.8
 ROOFTOP STRUCTURES AND EQUIPMENT.
  
 8C) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) NO WIND DESIGN CRITERIA WAS PROVIDED TO BE ABLE TO
 CALCULATE THE PRESSURES REQUIRED FOR COMMENT # 8B.
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
  
 9.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 9.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 9.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 9.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 9.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2)
  
 10) SHEET M1.1 SHOWS A GENERATOR BUT THERE IS NO
 INFORMATION ON THE SLAB, AND ANCHORING OF THE GENERATOR
 TO RESIST THE MOMENT OF OVERTURNING.
 2010 FBC-B 1609.6.4 WIND DESIGN PROCEDURE.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  