2015-06-08 09:59:17 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15050842 |
| ADD: 1100 W TECHNOLOGY PLACE # 104 |
| CONT: HEDRICK BROS. |
| TEL: (561)689-8880 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JUNE 08/2015 |
| ACTION: DENIED |
| |
| 1)SHEET A.01 THE PROJECT DATA INDICATES THE OCCUPANCY |
| AS A F1 OCCUPANCY. WHERE THE PLANS INDICATE A MIXED USE |
| OCCUPANCY BETWEEN A F-1 AND STORAGE OCCUPANCY AND |
| OFFICE AS A ACCESSORY OCCUPANCY. WHERE LESS THAN 10% OF |
| THE FLOOR AREA OF THE BUILDING IS USED IN A OCCUPANCY |
| TYPE IT IS CONSIDERED A ACCESSORY OCCUPANCY. OVER 10 % |
| OF THE BUILING FLOOR AREA IT IS CONSIDERED A MIXED USE |
| BUILDING. THE QUESTION IS IF THE STORAGE OCCUPANCY IS |
| TO BE CONSIDERED A S1 OR S2. THE S2 OCCUPANCY DOES |
| INCLUDE FROZEN FOODS, FOOD PRODUCT AND THIS IS THE |
| QUESTION, DAIRY PRODUCTS IN NONWAXED COATED PAPER |
| CONTAINERS? HOW IS THE ICE CREAM PACKAGED? |
| |
| 2) TABLE 508.4 DOES NOT REQUIRE OCCUPANCY SEPARATION |
| BETWEEN THE F1 & S1 WHEREAS THE F1 & S2 DOES REQUIRE |
| SEPARATION, 2 HR IF NON-SPRINKLERED & 1 HOUR FOR |
| SPRINKLERED. THE OTHER OPTION IS TO REVIEW THE |
| REQUIREMENTS OF NON-SEPARATED OCCUPANCIES FOUND UNDER |
| FBC-B 508.3. |
| |
| 3) THE OCCUPANCY COUNT IS TAKEN ON THE WHOLE OF THE |
| FACILITY BEING F1 AND THE OCCUPANT LOAD TAKEN AT 100 |
| SQ. FT/ PER OCCUPANT. STORAGE STOCK AND SHIPPING ARE TO |
| BE TAKEN AT 300 GROSS AND BUSINESS AT 100 GROSS. PLEASE |
| REVISE THE OCCUPANCY COUNT. 2010 FBC-B TABLE 1004.1.1. |
| |
| 4) THE COVERSHEET INDICATES THIS BUILDING NOT FIRE |
| SPRINKLERED AND ADDS THE STATEMENT EXIT TRAVEL 200 FT. |
| W/O FIRE SPRINKLERS. SHEET A.03 STATES THE BUILDING IS |
| FIRE SPRINKLERED BUT THE TRAVEL DISTANCE IS STILL AT |
| 200 FT, TAKEN FOR F1 NON-FIRE SPRINKLERED? SEE FBC-B |
| TABLE 1016.1. |
| |
| 5) THE SHEET A.03 SHOWS (2) NEW COOLER AND FREEZERS |
| COMBINED THEY ARE WELL OVER 400 SQ. FT. IN AREA. FBC-B |
| 2603.4.1.3 IN NON-SPRINKLERED BUILDINGS LIMITS THE AREA |
| TO A AGGREGATE AREA OF 400 SQ. FT. |
| |
| 6A) THE WALK IN CCOLER & FREEZERS ARE TO BE UNDER |
| SEPARATE PERMIT WITH ASSOCIATED FEES. THEY WILL NEED TO |
| SHOW COMPLIANCE WITH 2603.4.1.2 (1-4). THEY WILL ALSO |
| NEED TO SUPPLY FRAMING SPANS FOR THE WALLS & CEILING, |
| SHOW ALLOWABLE DEFLECTION LIMITS FBC-B TABLE 1604.3. |
| |
| 6B) THE FREEZER APPEARS IT MAY BE LARGER THAN 1000 SQ, |
| FT. IF SO IT WILL NEED TO COMPLY WITH 1015.5 ALSO SEE |
| EXCEPTION. PLEASE ALSO NOTE THAT FOR UNSPRINKLERED |
| BUILDINGS COMMON PATH OF TRAVEL IS LIMITED TO 50 FT. |
| FOR F & S OCCUPANCIES. SEE FBC-B 1014.3 EXCEPTION # 7. |
| |
| 7) SHEET M-5 SHOWS DETAILS FOR THE ROOF TOP A/H UNITS |
| ON CURBS. NOTE THERE ARE NO STRUCTURAL SHEETS SHOWING |
| THE NEW HOLES CUT INTO THE ROOF DECK, NOR IS THERE |
| INFORMATION IF THE EXISTING FRAMING SYSTEM WILL TAKE ON |
| THE ADDITIONAL POINT LOADING OR CONCENTRATED LOADS |
| WITHOUT ANY REINFORCEMENT? 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. FBC-B 1607.4. / 1607.11.1 |
| DISTRIBUTION OF ROOF LOADS. |
| |
| 8A) SHEET M5 SHOWS A DETAIL OF A NEW ROOF CURB BUT |
| THERE IS NO INFORMATION ON THE ATTACHMENT TO THE ROOF |
| FRAMING SYSTEM PART OF COMPONENTS & CLADDING, WILL NEED |
| TO SUBMIT PRODUCT APPROVAL FOR CURB. 2010 FBC-B |
| 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31) (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (G) PRE-ENGINEERED A/C STANDS, ROOF TOP CURBS |
| |
| 8B) THE OTHER ISSUE THIS SAME DETAIL INDICATES SEE THE |
| PRODUCT APPROVALS FOR THE ATTACHMENT OF THE AIR HANDLER |
| TO THE ROOFTOP CURB. THIS IS NOT PART OF A PRODUCT |
| APPROVAL AND WILL NEED TO BE ENGINEERED TO THE SITE |
| SPECIFIC JOBSITE CONDITIONS. SEE 2010 FBC-B 1609.8 |
| ROOFTOP STRUCTURES AND EQUIPMENT. |
| |
| 8C) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 9) NO WIND DESIGN CRITERIA WAS PROVIDED TO BE ABLE TO |
| CALCULATE THE PRESSURES REQUIRED FOR COMMENT # 8B. |
| WIND DESIGN CRITERIA |
| 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| |
| |
| 9.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 9.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 9.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 9.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 9.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| NEGATIVE TABLE 1609.2(2) |
| |
| 10) SHEET M1.1 SHOWS A GENERATOR BUT THERE IS NO |
| INFORMATION ON THE SLAB, AND ANCHORING OF THE GENERATOR |
| TO RESIST THE MOMENT OF OVERTURNING. |
| 2010 FBC-B 1609.6.4 WIND DESIGN PROCEDURE. |
| |
| 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |