2015-08-03 13:43:54 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY BUILDING (2300 N. JOG RD.) FOR IMPACT FEES |
| ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF |
| PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY |
| IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| CODE. |
| |
| ***RESPONSE: |
| RESPONSE LETTER STATES "PBC STAMPED PLANS AND COPY OF |
| RECEIPT IS ATTACHED". THERE ARE NO COUNTY STAMPED PLANS |
| AND NO COPY OF PAID RECEIPT SUBMITTED. |
| |
| 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC RULE 9N-3 FOR: |
| A) SINGLE HUNG WINDOWS ON THE NEW ADDITION. NOTE: THE |
| ADDITION IS NEW CONSTRUCTION. EVERYTHING IN THE |
| ADDITION NEEDS TO COMPLY WITH CURRENT CODE. |
| |
| ***RESPONSE: |
| THERE IS A HAND WRITTEN NOTE ON NOA 11-1013.12 |
| SUBMITTED STATING THAT "PGT WINDOWS SH4000 (RENAMED |
| SH200)". PROVIDE PROOF THAT WINDOW SERIES SH-4000 WERE |
| RE-NAMED SH-200. NEED TO VERIFY THAT SERIES 4000 AND |
| SERIES 200 WINDOWS ARE THE SAME. |
| |
| B) HURRICANE STORM SHUTTERS FOR NEW HORIZONTAL SLIDING |
| WINDOWS AND NEW SINGLE HUNG WINDOWS. AND, PROVIDE |
| COMPLETE INSTALLATION SCHEDULE. PLEASE VISIT THE CITY |
| WEBSITE FOR SAMPLE OF HURRICANE SHUTTERS INSTALLATION |
| SCHEDULE. PROTECTION OF OPENINGS IS REQUIRED BY SEC. |
| R301.2.1.2 OF 2010 FBC-RESIDENTIAL. |
| |
| ***RESPONSE: |
| (1) DRAWINGS SUBMITTED DON'T HAVE A FLORIDA PRODUCT |
| APPROVAL COVER PAGE OR MIAMI DADE NOA NUMBER. NEED |
| APPROVED PRODUCT APPROVAL OR MANUFACTURER MAY APPLY FOR |
| LOCAL PRODUCT APPROVAL. LOCAL PRODUCT APPROVALS ARE |
| APPROVED BY THE BUILDING OFFICIAL, ROBERT BROWN. |
| COMPLETE INFORMATION WITH ORIGINAL ENGINEER'S SEAL AND |
| SIGNATURES WILL NEED TO BE SUBMITTED FOR HIS REVIEW. |
| |
| (2) WHY DOOR #3 IS GOING TO HAVE SHUTTERS IF THE NOA |
| 12-0516.02 SUBMITTED IS LARGE AND SMALL MISSILE IMPACT |
| RESISTANT? |
| |
| (3) INSTALLATION SCHEDULE ON SHEET S-1 STATES THAT |
| SHUTTERS ARE GOING TO BE INSTALLED HORIZONTALLY. |
| PRODUCT APPROVAL SUBMITTAL DOESN'T ALLOW HORIZONTAL |
| INSTALLATION ON WOOD FRAMED BUILDINGS. SEE GENERAL NOTE |
| #7 ON FIRST PAGE OF SHUTTERS DRAWINGS FOR SECTIONS THAT |
| ALLOW HORIZONTAL INSTALLATION. |
| |
| 3- SPECIFY CARBON MONOXIDE ALARMS ON PLANS AS REQUIRED |
| BY SEC. R315 OF 2010 FBC-RESIDENTIAL. |
| |
| ***RESPONSE: |
| THERE ARE NO CARBON MONOXIDE ALARMS SHOWN ON THE |
| ELECTRICAL PLAN AND NEED THE CARBON MONOXIDE ALARMS FOR |
| ALL BEDROOMS (FRONT AND REAR UNIT). |
| |
| 4- SHEET A-1: SPECIFY SAFETY GLASS FOR THE ADDITION NEW |
| SINGLE HUNG WINDOWS ADJACENT TO THE NEW EXTERIOR DOOR. |
| SEC. R308.4(2) OF 2010 FBC-RESIDENTIAL. |
| |
| 5- TYP. SECTION ON SHEET S-1: |
| A) SPECIFY CROSS VENTILATION AS REQUIRED BY SEC. R806 |
| OF 2010 FBC-RESIDENTIAL. |
| |
| ***RESPONSE: |
| ENGINEER OF RECORD RESPONSE LETTER SAID "THE CEILING IN |
| THE ADDITION IS NOT FASTENED DIRECTLY TO THE RAFTERS |
| AND AS SUCH THERE IS CROSS VENTILATION AND R806 CROSS |
| VENTILATION IS NOT REQUIRED.". THIS IS NOT CORRECT. |
| CROSS VENTILATION IS REQUIRED OR ENGINEER OF RECORD MAY |
| DESIGN THE ROOF AS UNVENTED. SEE SEC. R806.4. |
| |
| B) COORDINATE SIZE OF BOTTOM PLATE WITH SIZE SPECIFIED |
| ON THE FOUNDATION ELEVATION S1 ON SAME SHEET. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| ***RESPONSE: |
| NOT DONE. |
| |
| C) CLARIFY IF THERE IS AN UNDER-FLOOR SPACE. IF SO, |
| THEN PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE |
| WITH SEC. R408 OF 2010 FBC-RESIDENTIAL. |
| |
| ***RESPONSE: |
| IT'S AN UNDER-FLOOR SPACE. VENTILATION WAS SPECIFIED. |
| NEED TO PROVIDE ACCESS AS REQUIRED BY SEC. R408.4 |
| |
| D) COORDINATE ATTACHMENT OF 2X8 LEDGER TO THE EXISTING |
| WALL WITH INFORMATION SHOWN ON FLOOR/WALL FRAMING PLAN. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| ***RESPONSE: |
| NOT DONE. |
| |
| 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS. REVISE |
| VALUATION AS REQUIRED. |
| |
| *** RESPONSE: |
| NEW VALUATION IS STILL TOO LOW. OVERHEAD AND PROFIT |
| STILL NEED TO BE CONSIDERED EVEN IF THE OWNER IS THE |
| GC. PROVIDE A COMPLETE ITEMIZED ESTIMATE FOR ALL THE |
| SCOPE OF WORK SHOWN ON PLANS. DESIGN PROFESSIONAL FEES |
| ARE TOO LOW ALSO. |
| |
| 7- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR THE NEW SINGLE HUNG WINDOWS ON THE NEW ADDITION. |
| SEC. R301. |
| |
| ***RESPONSE: |
| A TYPICAL WINDOW OPENING WAS PROVIDED BUT IT DOESN'T |
| MATCH ACTUAL CONDITIONS. REVISED PLANS SHOW A DOOR WITH |
| 2 WINDOWS ASSEMBLY. PROVIDE COMPLETE FRAMING DETAILS |
| FOR PROPOSED ASSEMBLY. |
| |
| 8- NEW COMMENT: SHEET A1 DOESN'T PROVIDE ANY |
| INFORMATION FOR THE NEW STEPS BY THE NEW ADDITION. |
| PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH |
| SEC. R311.7.4 |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REPLACE AND REMOVE ANY REVISED SHEET. PROVIDE |
| ORIGINAL DRAWIINGS FOR REFERENCE. |
| |