Plan Review Notes
Plan Review Notes For Permit 15050799
Permit Number 15050799
Review Stop B
Sequence Number 3
Notes
Date Text
2015-07-23 18:53:287/23/15 COMMENTS TO E-MAILED SECOND REVISED PLAN:
  
 MET WITH ROBERT BROWN THESE ARE THE COMMENTS
 1) POCKET DOORS ARE NOT ACCEPTABLE. HINGED SWING DOORS
 ARE OK.
  
 2) BEDROOM #2 IS SHOWN LIKE GOING THRU THE CLOSET TO GO
 TO THE PORCH. THIS IS NOT ALLOWED. CLEARLY SHOW THE
 CLOSET DOORS AND HALLWAY FROM BEDROOM TO THE DOOR
 LEADING TO THE PORCH.
  
 3) CLEARLY IDENTIFY WHICH WINDOWS ARE GOING TO BE
 REPLACED OR REMOVED. WINDOWS ON THE EXISTING FLOOR PLAN
 AND PROPOSED FLOOR PLAN DON'T MATCH. SEE NEW LIVING
 AREA ON REAR APARTMENT AND LIVING ROOM ON MAIN HOUSE.
 IS THE FIREPLACE GOING TO BE REMOVED? SPECIFY EGRESS
 WINDOWS FOR BEDROOM #1 ON REAR APARTMENT.
  
 4) PROPOSED PORCH DOOR. SEE FRIEDERIKE'S COMMENTS. NEED
 PRODUCT APPROVAL. MAKE SURE LANDING AND STEPS COMPLY
 WITH SEC. R311.3
  
  
  
  
 ORIGINAL COMMENTS:
 RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) FOR IMPACT FEES
 ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- ENGINEER OF RECORD TO REVISE ALTERATION LEVEL
 SPECIFIED ON SHEET S-1. REAR UNIT IS MORE THAN 50% WORK
 AREA AND THERE IS AN ADDITION ON THE FRONT UNIT.
 SPECIFY COMBINATION ALTERATION LEVELS AS REQUIRED BY
 SEC. 401.4 OF 2010 FBC-EXISTING BUILDING.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC RULE 9N-3 FOR:
 A) ROOF MATERIAL TO BE INSTALLED.
  
 B) SINGLE HUNG WINDOWS ON THE NEW ADDITION. NOTE: THE
 ADDITION IS NEW CONSTRUCTION. EVERYTHING IN THE
 ADDITION NEEDS TO COMPLY WITH CURRENT CODE.
  
 C) HURRICANE STORM SHUTTERS FOR NEW HORIZONTAL SLIDING
 WINDOWS AND NEW SINGLE HUNG WINDOWS. AND, PROVIDE
 COMPLETE INSTALLATION SCHEDULE. PLEASE VISIT THE CITY
 WEBSITE FOR SAMPLE OF HURRICANE SHUTTERS INSTALLATION
 SCHEDULE. PROTECTION OF OPENINGS IS REQUIRED BY SEC.
 R301.2.1.2 OF 2010 FBC-RESIDENTIAL.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ROOF
 FRAMING PLAN, WALL SECTIONS AND DETAILS. PROVIDE ONLY
 THE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO LIST THE
 FLORIDA PRODUCT APPROVAL NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- SPECIFY CARBON MONOXIDE ALARMS ON PLANS AS REQUIRED
 BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 6- BEDROOMS #2 AND #3 OF MAIN HOUSE DON'T COMPLY WITH
 THE EGRESS REQUIREMENTS. PROPOSED BEDROOM #3 WILL BLOCK
 THE EGRESS THAT WAS THERE FOR THESE TWO BEDROOMS. BASED
 ON CITY RECORDS, THERE IS A PORCH ON THE SOUTH SIDE OF
 THE BEDROOMS. THERE ARE DOORS LEADING TO THIS PORCH.
 CLOSING THE DOORS WILL CREATE A SAFETY HAZARD. SEC.
 601.2 OF 2010 FBC-EXISTING BUILDING.
  
 7- PROVIDE INFORMATION FOR EGRESS FOR PROPOSED BEDROOM
 #3 ON MAIN HOUSE SHOWING COMPLIANCE WITH SEC. R310 OF
 2010 FBC-RESIDENTIAL. NOTE: SEE COMMENT ABOVE REGARDING
 EGRESS FOR BEDROOM #2 AND #3.
  
 8- SIZE OF HORIZONTAL SLIDING WINDOW SHOWN ON THE PLANS
 FOR BEDROOM #2 AND #3 OF REAR UNIT IS NOT SHOWN ON THE
 PRODUCT APPROVAL SUBMITTED (NOA 12-1017.03). ARE THESE
 CUSTOM WINDOWS?. NOTE: CUSTOM WINDOWS REQUIRE BUILDING
 OFFICIAL APPROVAL. COMPLETE ENGINEERING PACKAGE WILL BE
 REQUIRED FOR REVIEW AND APPROVAL. FAC RULE 9N-3.
  
 9- SQUARE FOOTAGE FOR REAR UNIT IS INCORRECT. SEE FLOOR
 PLANS AND REVISE PROJECT DATA INFORMATION ON SHEET C-1
 AND SHEET A-1 AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 10- SHEET A-1:
 A) SPECIFY SAFETY GLASS FOR NEW SINGLE HUNG WINDOW
 ADJACENT TO THE NEW DOOR LEADING TO THE NEW BEDROOM #3.
 SEC. R308.4(2) OF 2010 FBC-RESIDENTIAL.
  
 B) SPECIFY ALL DIMENSIONS FOR NEW BEDROOM #1 ON REAR
 UNIT TO VERIFY COMPLIANCE WITH SEC. R304.3 OF 2010
 FBC-RESIDENTIAL. SPECIFY THE SHORTEST DIMENSION BETWEEN
 THE NEW CLOSET AND THE EXTERIOR WALL.
  
 11- ALL EXTERIOR ELEVATIONS ARE MISLABELED. EAST
 ELEVATION IS THE WEST ELEVATION NOT EAST. NORTH
 ELEVATION IS SOUTH ELEVATION NOT NORTH, ETC. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- EXTERIOR ELEVATIONS DON'T' MATCH PLANS. SEE NUMBER
 OF WINDOWS AND TYPE OF WINDOWS SHOWN ON PLANS AND
 REVISE ELEVATIONS TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 13- TYP. SECTION ON SHEET S-1:
 A) SPECIFY CROSS VENTILATION AS REQUIRED BY SEC. R806
 OF 2010 FBC-RESIDENTIAL.
  
 B) ROOF PITCH SPECIFIED ON THE EXTERIOR ELEVATION
 REQUIRES DOUBLE UNDERLAYMENT. PROVIDE SPECIFICATIONS.
 SEC. R905.2.2 OF CITY AMENDMENTS.
  
 C) PROVIDE COMPLETE SPECIFICATIONS FOR WOOD FLOOR JOIST
 SHOWING COMPLIANCE WITH SEC. R317.1 OF 2010
 FBC-RESIDENTIAL.
  
 E) SPECIFY ALL ROOF JOISTS CONNECTORS. SEC. R301.
  
 F) COORDINATE SIZE OF BOTTOM PLATE WITH SIZE SPECIFIED
 ON THE FOUNDATION ELEVATION S1 ON SAME SHEET. SEC.
 107.2.1 CITY AMENDMENTS.
  
 G) CLARIFY IF THERE IS AN UNDER-FLOOR SPACE. IF SO,
 THEN PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE
 WITH SEC. R408 OF 2010 FBC-RESIDENTIAL.
  
 H) PROVIDE COMPLETE INFORMATION FOR THE ROOF SHEATHING.
 SPECIFY SHEATHING THICKNESS AND NAIL SIZE AND SPACING
 SHOWING COMPLIANCE WITH SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL.
  
 I) COORDINATE ATTACHMENT OF 2X8 LEDGER TO THE EXISTING
 WALL WITH INFORMATION SHOWN ON FLOOR/WALL FRAMING PLAN.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 J) COORDINATE WALL SHEATHING INFORMATION WITH
 INFORMATION SHOWN ON FOUNDATION ELEVATION S1 ON SAME
 SHEET. SEC. 107.2.1 CITY AMENDMENTS.
  
 14- FOUNDATION ELEVATION DETAIL S1 ON SHEET S-1:
 A) REVISE FOUNDATION HEIGHT ABOVE FINISHED GRADE AS
 REQUIRED BY SEC, R404.1.6 OF 2010 FBC-RESIDENTIAL.
 (NEED 6" MIN.)
  
 B) SPECIFY ALL FLOOR JOISTS CONNECTORS. SEC. R301
  
 15- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS. REVISE
 VALUATION AS REQUIRED.
  
 16- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE NEW SINGLE HUNG WINDOWS ON THE NEW ADDITION.
 SEC. R301.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED SHEET. PROVIDE
 ORIGINAL DRAWIINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT