Plan Review Notes For Permit 15050799 |
Permit Number |
15050799 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-07-29 11:00:08 | 2ND REVIEW: FBC 2010 MECHANICAL | | | | 1) PROVIDE A MEANS OF RETURN FROM THE NE REAR LIVING | | AREA, AND THE SW CORNER ADDITION- SECTION M1602.4 | | FBC-10 RESIDENTIAL. PLEASE NOTE, DOOR UNDERCUTS DO NOT | | PROVIDE ADEQUATE RETURN AIR PER THE CODE- TRANSFER | | DUCTS OR TRANSFER GRILLS MUST ALSO BE INSTALLED | | 2) PROVIDE DETAILS FOR THE NEW AC DROP IN THE ADDITION | | AT SW CORNER. INDICATE: A) DUCT TYPE AND SIZE B) | | CONNECTION POINT TO THE MAIN SYSTEM C) DIFFUSER SIZE | | AND SUPPLY CFM. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|