2015-07-30 11:30:00 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE SECOND (2ND) REVIEW OF THE |
| ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH |
| REGARDS TO THE REQUIRED CORRECTIONS. THE FOLLOWING |
| ITEMS SHALL BE CORRECTED AND THE PLANS RESUBMITTED FOR |
| ANOTHER REVIEW. |
| |
| 1. THE RISER DIAGRAM MAY BE IN VIOLATION OF NEC 230.2 & |
| NEC 230.40. HAD THIS BEEN THE ONLY DEFICIENCY NOTED A |
| NOTE FOR THE FIELD INSPECTOR TO VERIFY COMPLIANCE WOULD |
| HAVE SOLVED THE PROBLEM, BUT OTHER ITEMS ARE MISSING AS |
| NOTED BELOW. |
| 2. RISER DIAGRAM, LOAD CALCS & PANEL SCHEDULE SHALL BE |
| SITE SPECIFIC. LOAD CALCS, PANEL SCHEDULE AND RISER |
| DIAGRAM AS SUBMITTED DO NOT MATCH. |
| 3. DEFINE ON THE ELECTRICAL PLAN THE AREA OF WORK. |
| 4. INDICATE ON THE ELECTRICAL PLAN WHERE IS ?MAIN HOUSE |
| BEDROOM 3?, AS DESCRIBED ON THE NOTES. |
| 5. ALL REPLACEMENT RECEPTACLES SHALL BE INSTALLED AS |
| DESCRIBED IN NEC 406.3(D)(1) THROUGH (D)(3). |
| 6. ALL NEW RECEPTACLES SHALL BE LISTED AS ?TAMPER |
| RESISTANT? AS INDICATED IN NEC 406.11. |
| 7. NEC 210.52(E)(1) REQUIRES THAT THERE BE A GFI OUTLET |
| IN BOTH THE FRONT AND REAR OF THE DWELLING. IF THE |
| SCOPE OF WORK ENCOMPASSES ANY WORK AT ANY OF THOSE |
| AREAS, THAT OUTLETS SHALL BE INSTALLED AS INSTRUCTED BY |
| NEC 406.8. |
| 8. SMOKE DETECTOR PLACEMENT AS REFLECTED ON THE |
| ELECTRICAL SHEET DOES NOT MEET THE FBC-R 314 OR 315 |
| REQUIREMENTS. DUE TO THIS ADDITION, SMOKE DETECTOR |
| COMPLIANCE SHALL BE ADHERED TO THROUGHOUT THE WHOLE |
| HOUSE. THESE DEVICES SHALL BE INTER-CONNECTED AS WELL. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |