 1ST REVIEW: FBC 2010 MECHANICAL
  
 1) ADDITIONAL DETAILS ARE REQUIRED FOR APPROVAL:
 A) PROVIDE AN AC LAYOUT PLAN: SHOW ALL NEW AND
 RELOCATED DUCTS, DIFFUSERS, RETURNS AND CONNECTION TO
 THE RELOCATED AIR HANDLER.
 B) PROVIDE A DIMENSIONED SECTION CUT OF THE NEW AIR
 HANDLER CLOSET VERIFYING COMPLIANCE WITH SECTION
 M1305.1.1 FBC-10 RESIDENTIAL: 4 INCHES CLEARANCE ALONG
 THE SIDES, BANK AND TOP WITH A TOTAL WIDTH OF THE
 ENCLOSING SPACE AT LEAST 12 INCHES WIDER THAN THE AIR
 HANDLER.
 C) INDICATE THE NEW CLOSET DOOR WILL BE A FULL LOUVERED
 TYPE FOR RETURN AIR.
  