2015-06-29 17:53:16FIRST ELECTRICAL REVIEW WAS FAILED AS INDICATED BELOW.
 YOU NEED TO SUBMIT AN ELECTRICAL PAGE REFLECTING THE
 FOLLOWING:
 1. ELECTRICAL LOAD CALCS FOR BOTH FRONT AND REAR HOME
 2. SITE SPECIFIC RISER DIAGRAM FOR EACH UNIT.
 3. PANEL SCHEDULE FOR EACH UNIT.
 4. EXISTING ELECTRICAL OUTLETS WITHIN THE AREA OF THE
 PROPOSED WORK
 5. WHATEVER OUTLETS WILL BE ADDED AS PART OF THE NEW
 WORK
 6. LOCATION OF ANY EXISTING SMOKE DETECTOR IF ANY
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME.