Plan Review Notes
Plan Review Notes For Permit 15050794
Permit Number 15050794
Review Stop G
Sequence Number 1
Notes
Date Text
2015-05-20 11:40:581) THE SUBMITTED PLAN REFER TO ELCTRICAL EQUIPMENT, A
 PROPOSED EQUIPMENT SHELTER, A 440 FT. TOWER, CONDUITS,
 ETC. SUBMIT A COMPLETE SET OF PLANS THAT INCLUDES
 DETAILS FOR THE ENTIRE SCOPE OF WORK TO BE DONE. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 2) PROVIDE ANCHORING DETAILS FOR THE TANK TO PREVENT
 FLOTATION.NFPA SEC. 6.6.1.6.
 3) INDICATE ON THE PLANS THAT THE LP TANK IS AN
 UNDERGROUND TANK.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4) SHOW THE SIZE OF THE TANK ON THE PLANS.WPB AMEND. TO
 2010 FBC SEC. 107.3.5.1.3.
 5) SHOW THE TOTAL DEVELOPED LENGTH FROM THE PROPANE
 TANK TO THE GENERATOR. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 6) SHOW THE SPACING OF THE BOLLARDS ON THE PLAN.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
  