Plan Review Notes
Plan Review Notes For Permit 15050792
Permit Number 15050792
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-05-20 15:48:12 
 WEST PALM BEACH MUNICIPAL CODE SECTION 38-46(B)(1) -
 TENT PERMIT: A PERMIT IS REQUIRED PRIOR TO ERECTION OF
 A TENT.
  
 NFPA 1 SECTION - 25.1.10.1.6 FLAMMABLE GAS: CONTAINERS
 FOR LIQUEFIED PETROLEUM GASES SHALL BE PLACED A MINIMUM
 OF 5 FEET FROM ANY TENT. TANKS SHALL BE SECURED IN THE
 UPRIGHT POSITION AND PROTECTED FROM VEHICULAR TRAFFIC.
  
 NFPA 1 SECTION - 25.1.12 GENERATORS: GENERATORS AND
 OTHER INTERNAL COMBUSTION ENGINES SHALL BE SEPARATED
 FROM TENTS BY A MINIMUM OF 5 FEET AND SHALL BE
 PROTECTED FROM CONTACT BY FENCING, ENCLOSURE OR OTHER
 APPROVED MEANS.
  
 NFPA 1 SECTION - 25.1.5.4 UNAUTHORIZED OPEN FLAME:
 UNAUTHORIZED OPEN FLAMES SHALL BE PROHIBITED IN ANY
 TENT OR TEMPORARY MEMBRANE STRUCTURE.
  
 NFPA 1 SECTION - 25.1.9 ELECTRICAL CORDS: CABLES ON THE
 GROUND IN AREAS TRAVERSED BY THE PUBLIC SHALL BE PLACED
 IN TRENCHES OR PROTECTED BY APPROVED COVERS.
  
 NFPA 1 SECTION - 25.2.1.2 TENT COVERAGE: TENTS SHALL BE
 ERECTED TO COVER NOT MORE THAN 75 PERCENT OF THE
 PREMISES.
  
 NFPA 1 SECTION - 25.2.2.1 FLAME SPREAD: ALL TENT FABRIC
 SHALL MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA
 CONTAINED IN NFPA 701, STANDARD METHODS OF FIRE TESTS
 FOR FLAME PROPAGATION OF TEXTILES AND FILMS. THE FLAME
 SPREAD CERTIFICATE MUST BE PROVIDED OR THE TENT CANNOT
 BE USED OR MUST BE REMOVED.
  
 NFPA 1 SECTION - 25.2.3.5 TENT PLACEMENT: THE PLACEMENT
 OF TENTS RELATIVE TO OTHER STRUCTURES SHALL BE AT THE
 DISCRETION OF THE AHJ. TENT TO BE LOCATED A MINIMUM OF
 10 FEET FROM ANY BUILDING, STRUCTURE, OR ADJACENT STAKE
 LINE UNLESS PREVIOUSLY AND DIRECTLY APPROVED BY THE
 FIRE MARSHAL.
  
 NFPA 1 SECTION - 25.2.4 FIRE HAZARDS: THE GROUND
 ENCLOSED BY ANY TENT AND THE GROUND FOR A REASONABLE
 DISTANCE BUT FOR NOT LESS THAN 10 FEET OUTSIDE OF SUCH
 A TENT, SHALL BE CLEARED OF ALL FLAMMABLE OR
 COMBUSTIBLE MATERIAL OR VEGETATION THAT IS NOT USED FOR
 NECESSARY SUPPORT EQUIPMENT. THE PREMISES SHALL BE KEPT
 FREE FROM SUCH FLAMMABLE OR COMBUSTIBLE MATERIALS
 DURING THE PERIOD FOR WHICH THE PREMISES ARE USED BY
 THE PUBLIC.
  
 NFPA 1 SECTION - 25.2.4.2 NO SMOKING SIGNS: SMOKING
 SHALL NOT BE PERMITTED IN ANY TENT. THE POSTING OF
 WEATHERPROOF NO SMOKING SIGNS IS REQUIRED.
  
 NFPA 1 SECTION - 25.2.5 FIRE-EXTINGUISHING EQUIPMENT:
 PORTABLE FIRE EXTINGUISHING EQUIPMENT OF APPROVED TYPES
 SHALL BE FURNISHED AND MAINTAINED IN TENTS IN SUCH
 QUANTITY AND IN SUCH LOCATIONS AS APPROVED BY THE AHJ.
 LARGE EVENTS SHALL HAVE EXTINGUISHERS WITHIN 75FT OF
 EACH OTHER; MINIMUM 10LB ABC, THIRD PARTY CERTIFIED AND
 TAGGED.
  
 NFPA 1 SECTION - 50.2.1.9 COOKING EQUIPMENT: COOKING
 EQUIPMENT USED IN FIXED, MOBILE, OR TEMPORARY
 CONCESSIONS, SUCH AS TRUCKS, BUSES, TRAILERS,
 PAVILIONS, TENTS, OR ANY FORM OF ROOFED ENCLOSURE,
 SHALL COMPLY WITH NFPA 96.
  
 NFPA 101 SECTION - 12.2.8 ILLUMINATION OF MEANS OF
 EGRESS & EXIT SIGNS: MEANS OF EGRESS, FOR TENTS
 EXCEEDING 1200 SQUARE FEET, SHALL BE ILLUMINATED AND
 PROVIDED WITH EMERGENCY LIGHTING.
  