Plan Review Notes
Plan Review Notes For Permit 15050767
Permit Number 15050767
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-28 10:09:04APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1)PROVIDE A PANEL SCHEDULE WITH OCPD AND WIRE SIZES.
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 2) PANEL TO BE USED AS JUNCTION BOX TO COMPLY WITH NEC
 314
  
 3) RACEWAY CONDUIT FILL FOR BRANCH CIRCUITS TO COMPLY
 WITH NEC 310.16, TABLES 4 AND 8, AND ANNEX C.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]