Plan Review Notes
Plan Review Notes For Permit 15050732
Permit Number 15050732
Review Stop P
Sequence Number 1
Notes
Date Text
2015-06-09 09:28:011) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO 2010
 FBC SEC. 107.3.5.1.3.
 2) THE WASHING MACHINE SHALL BE ON A 3 INCH STACK PER
 THE 2010 FPC SEC.406.3.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE TANKLESS WATER HEATER. WPB AMEND.TO 2010
 FBC SEC. 107.2.1.
 4) CLEANOUTS ARE REQUIRED IN WASTE STACKS PER 2010 FPC
 SEC.708.3.4.
 5) THE SINK IN THE BREAK ROOM SHALL COMPLY WITH THE FL.
 ACCESS. CODE SEC. 212, 606.1- 606.5. THE MAXIMUM HEIGHT
 SHALL BE 34 INCHES. SHOW THIS ON BOTH SETS OF PLANS.
 6) SHT. S-1 SHOWS THE OCCUPANCY TYPE AS MERCANTILE AND
 THE GENERAL BUILDING CODE ANALYSIS BOX ON E-1 NOTES THE
 OCCUPANCY AS BUSINESS.CLARIFY. ALSO, THE BOX ON SHT.
 E-1 DOES NOT APPEAR TO BE FOR THIS SPACE. THE TENANT
 SPACE IS LISTED AS 6300 SQ.FT. AND SHT. S-1 NOTES THIS
 SPACE AS 1300 SQ. FT.THERE IS ALSO A DIS
 7) THIS OCCUPANCY SHALL BE CLASSIFIED PER SEC. 302 OF
 THE 2010 - FBC-BUILDING.INDICATE THE CORRECT OCCUPANCY
 ON BOTH SHEETS OF BOTH SETS OF PLANS.
 8) THERE IS ALSO A DISCREPANCY IN THE TYPE OF
 CONSTRUCTION ON THE PLANS.SHT. S-1 NOTES THE TYPE OF
 CONSTRUCTION AS TYPE III (ZONING 7 OCCUPANCY BOX) & AS
 TYPE IIB (CODE INFORMATION BOX) AND AS TYPE IIB ON SHT.
 E-1. CLARIFY.
  