2015-06-10 15:43:171ST REVIEW: FBC 2010 MECHANICAL
  
 1) MINIMUM VENTILATION CALCULATIONS ARE REQUIRED FOR
 THE PROPOSED NEW FOOT MASSAGE BUSINESS IN COMPLIANCE
 WITH SECTION 709.1 FBC-10 EXISTING BUILDING. PLEASE SEE
 TABLE 403.3 FBC-10 MECHANICAL AND PROVIDE A TABLE ON
 THE PLAN INDICATING THE TOTAL CFM'S OF REQUIRED OUTDOOR
 AIR, AND THE TOTAL OUTDOOR AIR THAT IS BEING PROVIDED
 TO THE SPACES BY THE EXISTING SYSTEMS, OR BY ANY
 PROPOSED NEW SYSTEMS.
 2) PROVIDE AN AC LAYOUT PLAN INDICATING THE LOCATIONS
 OF ALL SUPPLY AND RETURN DUCTS, DIFFUSERS AND GRILLS.
 PROVIDE NOTES AND SYMBOLS ON THE PLAN TO CLEARLY
 INDICATE WHAT COMPONENTS ARE EXISTING, RELOCATED, OR
 NEWLY INSTALLED.
 3) PLEASE REMOVE THE SUBMITTED MANUAL J AC
 CALCULATIONS. ACCA MANUAL J IS A CALCULATION METHOD FOR
 RESIDENTIAL AC SYSTEMS. IF NEW AC SYSTEM IS PROPOSED,
 THE SIZING CALCULATION SHALL BE PERFORMED IN ACCORDANCE
 WITH ACCA MANUAL N OR ASHRAE STANDARD 183- SECTION
 503.2.1 FBC-10 ENERGY CONSERVATION
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  