2015-06-10 15:43:17 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | 1) MINIMUM VENTILATION CALCULATIONS ARE REQUIRED FOR | | THE PROPOSED NEW FOOT MASSAGE BUSINESS IN COMPLIANCE | | WITH SECTION 709.1 FBC-10 EXISTING BUILDING. PLEASE SEE | | TABLE 403.3 FBC-10 MECHANICAL AND PROVIDE A TABLE ON | | THE PLAN INDICATING THE TOTAL CFM'S OF REQUIRED OUTDOOR | | AIR, AND THE TOTAL OUTDOOR AIR THAT IS BEING PROVIDED | | TO THE SPACES BY THE EXISTING SYSTEMS, OR BY ANY | | PROPOSED NEW SYSTEMS. | | 2) PROVIDE AN AC LAYOUT PLAN INDICATING THE LOCATIONS | | OF ALL SUPPLY AND RETURN DUCTS, DIFFUSERS AND GRILLS. | | PROVIDE NOTES AND SYMBOLS ON THE PLAN TO CLEARLY | | INDICATE WHAT COMPONENTS ARE EXISTING, RELOCATED, OR | | NEWLY INSTALLED. | | 3) PLEASE REMOVE THE SUBMITTED MANUAL J AC | | CALCULATIONS. ACCA MANUAL J IS A CALCULATION METHOD FOR | | RESIDENTIAL AC SYSTEMS. IF NEW AC SYSTEM IS PROPOSED, | | THE SIZING CALCULATION SHALL BE PERFORMED IN ACCORDANCE | | WITH ACCA MANUAL N OR ASHRAE STANDARD 183- SECTION | | 503.2.1 FBC-10 ENERGY CONSERVATION | | | | CHRISTOPHER COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|