Plan Review Notes
Plan Review Notes For Permit 15050702
Permit Number 15050702
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-02 18:53:03THE LOAD CALCS YOU SUBMITTED CALL FOR A 60KW GENERATOR,
 YOUR SUBMITTAL PACKAGE REFLECTS A 48 KW UNIT. YOU WILL
 NEED THE AUXILIARY TRANSFER SWITCH CONTACT KIT TO SHED
 UNNECESSARY LOAD UNDER EMERGENCY CONDITIONS.