2015-06-02 17:25:23IMPORTANT NOTICE:
 1. BOAT LIFT MOTORS SHALL HAVE GFI PROTECTION PER NEC
 2108(C).
 2. TAKE VOLTAGE DROP & TEMPERATURE EXPOSURE INTO
 ACCOUNT WHEN SIZING CONDUCTORS.
 3. CHECK OUTLETS IN DOCK PEDESTAL FOR COMPLIANCE W/NEC
 406.8 (WR RATED)
  