2015-10-02 10:42:53 | 3RD REVIEW: FBC 2010 |
| |
| THE PLANS DO NOT CONTAIN SUFFICIENT CLARITY TO INDICATE |
| THE WORK PROPOSED OR SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| SECTION 107.3.5). |
| |
| PLEASE RESOLVE THE FOLLOWING CONFLICTS OR PROVIDE |
| ADDITIONAL DETAIL IN THE SUBMITTED DRAWINGS AS FOLLOWS: |
| |
| 1. INCORPORATE SHEET S-0 INTO THE DRAWING SET IF IT IS |
| INTENDED THAT IT REMAIN PART OF THE SUBMITTAL. |
| 2. SHEET S-0 INDICATES BUILDING C WILL HAVE NO WORK |
| DONE ON IT YET SHEET S-1 STATES "NEW WORK IN THIS |
| BUILDING." |
| 3. SHEET S-1 FLOOR PLAN SHOWS A SECTION A IS ON SHEET |
| S-1 BUT NO SECTION A EXIST. |
| 4. SHEET S-1 INDICATES NEW CONCRETE FLOOR BUT HAS NO |
| DETAIL. |
| 5. INSULATION VALUES ON PLAN V. ENERGY SUBMITTAL |
| CONFLICT. |
| 6. INADEQUATE DETAILS ARE PROVIDED FOR THE APPLICATION |
| OF STUCCO. |
| 7. COVERED PATION FOUNDATION DETAILS LACK BASIC |
| REEQUIRED INFORMATION. |
| 8. ELEVATIONS AND DETAILS PROVIDED ARE NOT COORDINATED |
| WITH PLAN. |
| |
| NOTE; IN GENERAL, THIS PLAN IS DEFICIENT TO THE POINT |
| THAT A REVIEW CANNOT BE EFFICIENTLY PERFORMED. IT IS |
| SUFFICIENT TO STATE THAT THE ENGINERE OF RECORD SHOULD |
| FULLY RE-EVALUATE THIS PLAN. |
| |
| |
| GENERAL COMMENTS FROM 1ST & 2ND REVIEW ARE BELOW: |
| |
| |
| MINIMUM PLAN REVIEW CRITERIA SHALL BE PROVIDED PER FBC |
| 107 TO INCLUDE BUT NOT LIMITED TO: |
| |
| 1.AN ENERGY SUBMITTAL |
| |
| 2.PRODUCT APPROVALS FOR WINDOWS & ROOFING FBC 107.3.4 - |
| PROVIDE PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| REGULATED BY |
| FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, |
| WINDOW, AND DOOR SUBMITTALS. |
| |
| 3.STRUCTURAL DETAILS FOR THE NEW OVERHANGS |
| |
| 4. OPEN CONDITION WHERE EXISTING SHUTTERS ARE PROPOSED |
| TO BE REMOVED |
| |
| STEVEN KENNEDY, CBO |
| CHIEF PLANS EXAMINER |