Plan Review Notes For Permit 15050614 |
Permit Number |
15050614 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-30 09:14:06 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | REVISION IS DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE OPENING NUMBERS DO NOT CORRESPOND TO THE KEY | | PLANS WHICH ARE SHEETS A1.0, A1.1, A1.2 AND A1 OF THE | | APPROVED MASTER PLANS (#14040895). ALSO REFER TO THE | | WINDOW AND DOOR SCHEDULE FOR 'B' UNIT ON SHEET A3.0. | | FBC 107.2.1 | | | | 2) THE MINIMUM EDGE DISTANCE FOR THE 1/4" SOLID SET | | ANCHORS IS LISTED AS 3.5" FOR BOTH CONCRETE AND | | CONCRETE BLOCK IN THE TABLE ON SHEET 9. THE EDGE | | DISTANCE ON THE INSTALLATION SCHEDULE IS SPECIFIED AS | | 2.5". IF USING A 2.5" EDGE DISTANCE THE TABLE IN THE | | PRODUCT APPROVAL REQUIRES THE ANCHOR SPACING TO BE | | REDUCED BY HALF. YOU WILL NEED TO REVISE THE EDGE | | DISTANCE OR THE ANCHOR SPACING IN THE INSTALLATION | | SCHEDULE. | | |
|