Plan Review Notes For Permit 15050612 |
Permit Number |
15050612 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-27 09:39:15 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | REVISION IS DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE OPENING NUMBERS DO NOT CORRESPOND TO THE KEY | | PLANS WHICH ARE SHEETS A1.0 AND A2.0 OF THE APPROVED | | MASTER PLANS (#14070510). ALSO REFER TO THE WINDOW AND | | DOOR SCHEDULE FOR 'F' UNIT ON SHEET A4.0. FBC 107.2.1 | | | | 2) THE MINIMUM EDGE DISTANCE FOR THE 1/4" SOLID SET | | ANCHORS IS LISTED AS 3.5" FOR BOTH CONCRETE AND | | CONCRETE BLOCK IN THE TABLE ON SHEET 9. THE EDGE | | DISTANCE ON THE INSTALLATION SCHEDULE IS SPECIFIED AS | | 2.5". IF USING A 2.5" EDGE DISTANCE THE TABLE IN THE | | PRODUCT APPROVAL REQUIRES THE ANCHOR SPACING TO BE | | REDUCED BY HALF. YOU WILL NEED TO REVISE THE EDGE | | DISTANCE OR THE ANCHOR SPACING IN THE INSTALLATION | | SCHEDULE. | | |
|