2015-08-13 11:44:13 | MECHANICAL APPROVED WITH EXCEPTION. |
| 8/13/15 |
| |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). |
| |
| 1) ACCESS PANELS REQUIRED FOR FIRE DAMPERS AT THE |
| FIRE-RATED DORMITORY CORRIDOR/ASSEMBLY OCCUPANCY |
| SEPARATION WALLS- SECTION 607.4 ACCESS AND |
| IDENTIFICATION. |
| FIRE AND SMOKE DAMPERS SHALL BE PROVIDED WITH AN |
| APPROVED MEANS OF ACCESS, LARGE ENOUGH TO PERMIT |
| INSPECTION AND MAINTENANCE OF THE DAMPER AND ITS |
| OPERATING PARTS. THE ACCESS SHALL NOT AFFECT THE |
| INTEGRITY OF FIRE-RESISTANCE-RATED ASSEMBLIES. THE |
| ACCESS OPENINGS SHALL NOT REDUCE THE FIRE-RESISTANCE |
| RATING OF THE ASSEMBLY. ACCESS POINTS SHALL BE |
| PERMANENTLY IDENTIFIED ON THE EXTERIOR BY A LABEL |
| HAVING LETTERS NOT LESS THAN 0.5 INCH (12.7 MM) IN |
| HEIGHT READING: FIRE/SMOKE DAMPER, SMOKE DAMPER OR FIRE |
| DAMPER. ACCESS DOORS IN DUCTS SHALL BE TIGHT FITTING |
| AND SUITABLE FOR THE REQUIRED DUCT CONSTRUCTION. |
| 2) PROVIDE A PRODUCT SAUBMITTAL PACKAGE THAT INCLUDES |
| THE REVISED ENERGY CALCULATIONS, AND MANUFACTURER'S |
| SPECIFICATIONS FOR THE AC UNITS, FIRE DAMPERS, |
| MOTORIZED O/A DAMPERS, VAV BOXES, AND THE DUCT SMOKE |
| DETECTORS. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |