Plan Review Notes
Plan Review Notes For Permit 15050575
Permit Number 15050575
Review Stop B
Sequence Number 2
Notes
Date Text
2015-08-11 12:16:06BUILDING PLAN REVIEW
 W. P. B. REVISION: 15050575
 W. P. B. PERMIT: 14120580
 ADD: 901 45TH ST. QUANTUM HOUSE
 CONT: HEDRICK BROTHERS
 TEL: ( 561)689-8880
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: TUES. AUG. 11/ 2015
 ACTION: DENIED
  
 1) 2ND REQUEST. SHEET M1.1 SHOWS THE EAST WEST CORIDORS
 WITH FIRE DAMPERS AT THE FIRE RATED DORMITORY/ ASSEMBLY
 OCCUPANCY SEPARATION WALLS. PLEASE PROVIDE COMPLIANCE
 WITH THE 2010 FBC-B SECTION 716.4 ACCESS AND
 IDENTIFICATION. THIS SHOULD OCCUR AT ALL FIRE DAMPERS
 ON SITE.
 RESPONSE INDICATES SEE M5.1 DETAIL # 9. PLEASE NOTE
 THIS IS A WALL SECTION DETAIL OF A FIRE DAMPER LOCATED
 IN A RATED WALL. IR DOES NOT PROVIDE HOW YOU WILL GAIN
 ACCESS THROUGH A GYPSUM CEILING OR IDENTIFICATION FOR
 THE FIRE DAMPER.
  
 THE PRIME PERMIT # 14120580 SHEET 013-A1.5 AND SHEET
 015-A1.7 NORTH PARTIAL CEILING PLAN SHOWS GYPSUM
 CEILINGS ON BOTH SIDES OF THE RATED WALL AND DOORWAY.
 THE DUCTWORK AND FIRE DAMPER ARE INSTALLED BETWEEN THE
 2 CEILINGS. PLEASE ALSO SEE SHEET 025-A4.0 AND 026-A4.1
 SHOW THE 2 DIFFERENT ELEVTIONS OF CEILINGS, THE UPPER
 CEILING RATED PER U. L. P531.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2015-08-11 12:02:56BUILDING PLAN REVIEW
 W. P. B. REVISION: 15050499
 W. P. B. PERMIT: 14120580
 ADD: 901 45TH ST. QUANTUM HOUSE
 CONT: HEDRICK BROTHERS
 TEL: ( 561)689-8880
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 24/ 2015
 ACTION: DENIED
  
 1) SHEET M1.1 SHOWS THE EAST WEST CORIDORS WITH FIRE
 DAMPERS AT THE FIRE RATED DORMITORY/ ASSEMBLY OCCUPANCY
 WALLS. PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B
 SECTION 716.4 ACCESS AND IDENTIFICATION. THIS SHOULD
 OCCUR AT ALL FIRE DAMPERS ON SITE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  