2015-06-23 11:36:231ST REVIEW: FBC 2010 MECHANICAL
  
 1) PROVIDE REVISED ENERGY CALCULATIONS SHOWING THE
 COMPLIANCE DATA FOR THE NEW AC UNITS.
 2) SHEET M0.1: PROVIDE THE OUTDOOR AIR CALCULATIONS FOR
 THE GUEST ROOMS PER TABLE 403.3 FBC-10 MECHANICAL.
 3) SHEETS M0.1 & M1.1: THE REQUIRED 108 CFM'S OF
 OUTDOOR AIR FOR THE GUEST ROOM CORRIDORS SHOWN IN THE
 SCHEDULE IS NOT BEING SUPPLIED: PLEASE NOTE THE MINI
 SPLIT SYSTEMS AC-1A AND AC-1B ARE DUCTLESS.
 4) M1.1: THE AC-1A &1B CASSETTES APPEAR TO BE MOUNTED
 IN THE FIRE-RATED CORRIDOR CEILING MEMBRANE. INDICATE
 HOW THESE OPENINGS ARE GOING TO PROTECTED FROM FIRE AND
 SMOKE INTRUSION- REFERENCE SECTION 607.6.2 FBC-10
 MECHANICAL.
 5) M1.1 THE RETURN AIR GRILLS AND SUPPLY DUCTS ABOVE
 THE EAST AND WEST CORRIDOR FIRE DOORS IN THE CORRIDOR
 CEILINGS MUST BE PROTECTED WITH FIRE/SMOKE DAMPERS.
 PROVIDE A SCHEDULE ON THE PLANS INDICATING THE MAKES,
 MODELS, TYPES, SIZES, AND FIRE-RESISTANCE RATINGS OF
 THESE DAMPERS, AND ALL REQUIRED DAMPERS TO BE INSTALLED
 IN THE CORRIDORS AND GUEST ROOMS. NOTE: ALL DAMPER
 ACCESS DOORS LOCATED IN THE CORRIDOR AND GUEST ROOM
 CEILINGS SHALL BE FIRE-RATED. PROVIDE DETAILS AND
 SUBMIT SPECS FOR ALL PRODUCTS REVIEWED AND STAMPED BY
 THE DESIGN PROFESSIONAL OF RECORD.
 6) M1.1: SHOW THE LOCATIONS OF THE CONDENSER UNITS FOR
 AC-1A & 1B, AND PROVIDE INSTALLATION DETAILS.
 7) M1.1: FIRE/SMOKE DAMPERS ARE REQUIRED FOR THE
 EXHAUST DUCTS PENENTRATING THE EAST AND WEST RATED
 CORRIDOR WALLS, UNLESS CLAIMING ONE OF THE EXCEPTIONS
 UNDER SECTION 607.5.3: PLEASE PROVIDE DETAUILS
 INDICATING COMPLIANCE.
 8) M1.1: SHOW THE O/A SUPPLY DUCT FOR AC-2.
 9) PROVIDE A NARRATIVE INDICATING HOW THE DUCT SMOKE
 DETECTORS WILL BE SUPERVISED RELATING TO THE FIRE ALARM
 SYSTEM AND THE FAN SHUT SEQUENCE OF OPERATION. CLARIFY
 IS AC-1A & 1B WILL BE LINKED TO THE SYSTEM.
 10) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 DETAILS FOR ALL OF THE AIR HANDLERS- SECTION 307 FBC-10
 MECH.
 11) PROVIDE REFRIGERANT PIPING DETAILS INCLUDING PIPING
 MATERIAL, PIPING INSULATION, PIPING RUNS AND THROUGH
 PENETRATION FIRE-STOPPING DETAILS. INDICATE THE AMOUNT
 OF REFRIGERANT CHARGE IN LBS. FOR AC-1.
 12) PROVIDE HANGING AND SUPPORT DETAILS FOR THE VAV
 BOXES AND DUCTS.
 13) PROVIDE A SUBMITTAL PACKAGE FROM THE DESIGN
 PROFESSIONAL OF RECORD THAT INCLUDES THE AC UNITS, THE
 FIRE/SMOKE DAMPERS, THE DUCT SMOKE DETECTORS, THE
 MOTORIZED O/A DAMPERS, AND THE VAV BOXES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER