Notes |
Date |
Text |
2015-07-14 09:33:34 | THE FOLLOWING CORRECTIONS TO THE PLANS SHALL BE MADE | | FOR A SUCCESSFUL ELECTRICAL REVIEW. | | 1. PROVIDE/INCLUDE ELECTRICAL SPECS FOR THE PROPOSED | | CHILLERS. | | 2. PROVIDE LOAD CALCS FOR THE SOURCE PANELS | | 3. PROVIDE A PANEL SCHEDULE | | 4. INCLUDE PANEL P4 IN THE RISER DIAGRAM. |
|