2015-07-06 15:34:30BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050569
 ADD: 250 S. AUSTRALIAN AVE.
 CONT: EDD HELMS AIR CONDITIONING & ELEC.
 TEL: (305)653-2530
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 06/2015
 ACTION: DENIED
  
 1) SHEETS M1 & M3 BOTH SHOW THE REPLACEMENT OF THE
 CHILLER UNITS. THE PLANS DO NOT INDICATE HOW THE UNITS
 ARE GOING TO BE REMOVED AND REPLACED WITHOUT DAMAMGE TO
 THE BUILDING? WILL PORTIONS OF EITHER THE ROOF OR WALLS
 TO BE REMOVED AND REPLACED FOR THE REPLACEMENT OF
 UNITS? 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED. PLEASE PROVIDE
 DETAILS.
  
 2) SHEET M-3 SHOWS A WALL FIRE DAMPER BUT NOT A FIRE
 RATING IN ACCORDANCE WITH 2010 FBC-B 716.3.2 DAMPER
 RATING. TABLE 716.3.2.1.
  
 3) SHEET M-2 INDICATES A NEW EXHAUST FAN EF-CR-1 WHAT
 APPEARS TO BE A NEW ROOF TOP EXHAUST FAN, PLEASE
 PROVIDE DETAILS OF THE NEW ROOF TOP PENETRATION. NEW
 ROOF TOP CURB AND PRODUCT APPROVALS FOR NEW ROOF TOP
 UNIT. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS ROOF TOP EXHAUST FANS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) EXHAUST FANS TO COMPLY WITH 2010 FBC-B 1609.8 ROOF
 TOP STRUCTURES AND EQUIPMENT.
  
 6) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
  
 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 6.2AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 6.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  