2015-07-06 15:34:30 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15050569 |
| ADD: 250 S. AUSTRALIAN AVE. |
| CONT: EDD HELMS AIR CONDITIONING & ELEC. |
| TEL: (305)653-2530 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JULY 06/2015 |
| ACTION: DENIED |
| |
| 1) SHEETS M1 & M3 BOTH SHOW THE REPLACEMENT OF THE |
| CHILLER UNITS. THE PLANS DO NOT INDICATE HOW THE UNITS |
| ARE GOING TO BE REMOVED AND REPLACED WITHOUT DAMAMGE TO |
| THE BUILDING? WILL PORTIONS OF EITHER THE ROOF OR WALLS |
| TO BE REMOVED AND REPLACED FOR THE REPLACEMENT OF |
| UNITS? 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. PLEASE PROVIDE |
| DETAILS. |
| |
| 2) SHEET M-3 SHOWS A WALL FIRE DAMPER BUT NOT A FIRE |
| RATING IN ACCORDANCE WITH 2010 FBC-B 716.3.2 DAMPER |
| RATING. TABLE 716.3.2.1. |
| |
| 3) SHEET M-2 INDICATES A NEW EXHAUST FAN EF-CR-1 WHAT |
| APPEARS TO BE A NEW ROOF TOP EXHAUST FAN, PLEASE |
| PROVIDE DETAILS OF THE NEW ROOF TOP PENETRATION. NEW |
| ROOF TOP CURB AND PRODUCT APPROVALS FOR NEW ROOF TOP |
| UNIT. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(G) PRE-ENGINEERED A/C STANDS ROOF TOP EXHAUST FANS |
| |
| 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 5) EXHAUST FANS TO COMPLY WITH 2010 FBC-B 1609.8 ROOF |
| TOP STRUCTURES AND EQUIPMENT. |
| |
| 6) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| |
| 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 6.2AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 6.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| TABLE 1609.2(2) . |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |