 PROJECT: ELECTRICAL BUILDOUT
 PERMIT#: 14060946
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW REVISION#15050566
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) TWO COMPLETE COPIES OF PLANS INDICATING CLEARLY,
 ONLY THE CHANGES IN THE SCOPE OF WORK FOR
 CLARIFICATION. WPB AMENDMENTS TO THE FBC 107.3.1
 CONSTRUCTION DOCUMENTS.
  
 2) PROVIDE A COMPLETE PANEL SCHEDULE INDICATING EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 3) INDICATE THE CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORRESPONDING TO THE CIRCUIT NUMBERS IN THE PANEL
 SCHEDULE. WPB AMENDMENTS TO THE FBC 107.3.5.1.2
 ELECTRICAL
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.