2015-05-15 12:28:03 | 5/15/2015 |
| PROJECT: ELECTRICAL BUILDOUT |
| PERMIT#: 14060946 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW REVISION#15050566 |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) TWO COMPLETE COPIES OF PLANS INDICATING CLEARLY, |
| ONLY THE CHANGES IN THE SCOPE OF WORK FOR |
| CLARIFICATION. WPB AMENDMENTS TO THE FBC 107.3.1 |
| CONSTRUCTION DOCUMENTS. |
| |
| 2) PROVIDE A COMPLETE PANEL SCHEDULE INDICATING EVERY |
| CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| PURPOSE OR USE. NEC 408.4 |
| |
| 3) INDICATE THE CIRCUIT NUMBERS ON THE FLOOR PLAN |
| CORRESPONDING TO THE CIRCUIT NUMBERS IN THE PANEL |
| SCHEDULE. WPB AMENDMENTS TO THE FBC 107.3.5.1.2 |
| ELECTRICAL |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |