2015-05-26 19:21:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE OPENING NUMBERS DO NOT CORRESPOND TO THE KEY
 PLANS WHICH ARE SHEETS A1.0 AND A2.0 OF THE APPROVED
 MASTER PLANS (#14070510). ALSO REFER TO THE WINDOW AND
 DOOR SCHEDULE FOR 'A' UNIT ON SHEET A4.0. FBC 107.2.1
  
 2) THE MINIMUM EDGE DISTANCE FOR THE 1/4" SOLID SET
 ANCHORS IS LISTED AS 3.5" FOR BOTH CONCRETE AND
 CONCRETE BLOCK IN THE TABLE ON SHEET 9. THE EDGE
 DISTANCE ON THE INSTALLATION SCHEDULE IS SPECIFIED AS
 2.5". IF USING A 2.5" EDGE DISTANCE THE TABLE IN THE
 PRODUCT APPROVAL REQUIRES THE ANCHOR SPACING TO BE
 REDUCED BY HALF. YOU WILL NEED TO REVISE THE EDGE
 DISTANCE OR THE ANCHOR SPACING IN THE INSTALLATION
 SCHEDULE.
  