2015-05-16 12:22:27BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050533
 ADD: 622 N. FLAGLER DR. SUITE # 903
 CONT: BRANCH
 TEL: (561)833-6206
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. MAY 16/ 2015
 ACTION: DENIED
  
 1) SHEET A2.0 HAS 25 NOTES ON THE SHEET RELATING TO THE
 SCOPE OF WORK THAT IS RELATED TO THIS PROJECT. 20 OF
 THESE NOTES REFER TO THE INTERIOR DESIGNERS DRAWINGS.
 THERE WERE NO SUCH PLANS SUBMITTED UNDER THIS REVIEW.
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2) THE MISSING INTERIOR DESIGNER DRAWINGS MUST MEET THE
 FOLLOWING FLORIDA STATUTE: 481.2131?INTERIOR DESIGN;
 PRACTICE REQUIREMENTS; DISCLOSURE OF COMPENSATION FOR
 PROFESSIONAL SERVICES.? (1)?A REGISTERED INTERIOR
 DESIGNER IS AUTHORIZED TO PERFORM ?INTERIOR DESIGN? AS
 DEFINED IN S. 481.203. INTERIOR DESIGN DOCUMENTS
 PREPARED BY A REGISTERED INTERIOR DESIGNER SHALL
 CONTAIN A STATEMENT THAT THE DOCUMENT IS NOT AN
 ARCHITECTURAL OR ENGINEERING STUDY, DRAWING,
 SPECIFICATION, OR DESIGN AND IS NOT TO BE USED FOR
 CONSTRUCTION OF ANY LOAD-BEARING COLUMNS, LOAD-BEARING
 FRAMING OR WALLS OF STRUCTURES, OR ISSUANCE OF ANY
 BUILDING PERMIT, EXCEPT AS OTHERWISE PROVIDED BY LAW.
 INTERIOR DESIGN DOCUMENTS THAT ARE PREPARED AND SEALED
 BY A REGISTERED INTERIOR DESIGNER MAY, IF REQUIRED BY A
 PERMITTING BODY, BE SUBMITTED FOR THE ISSUANCE OF A
 BUILDING PERMIT FOR INTERIOR CONSTRUCTION EXCLUDING
 DESIGN OF ANY STRUCTURAL, MECHANICAL, PLUMBING,
 HEATING, AIR-CONDITIONING, VENTILATING, ELECTRICAL, OR
 VERTICAL TRANSPORTATION SYSTEMS OR THAT MATERIALLY
 AFFECT LIFE SAFETY SYSTEMS PERTAINING TO FIRE SAFETY
 PROTECTION SUCH AS FIRE-RATED SEPARATIONS BETWEEN
 INTERIOR SPACES, FIRE-RATED VERTICAL SHAFTS IN
 MULTISTORY STRUCTURES, FIRE-RATED PROTECTION OF
 STRUCTURAL ELEMENTS, SMOKE EVACUATION AND
 COMPARTMENTALIZATION, EMERGENCY INGRESS OR EGRESS
 SYSTEMS, AND EMERGENCY ALARM SYSTEMS.
 3) SHEET A2.0 NOTES 4,5,13,14 & 17 ALL DEAL WITH THE
 INTERIOR DESIGNERS PLANS, PLEASE NOTE THIS BUILDING WAS
 BUILT AFTER MARCH 13. 1991 AND MUST MEET THE FAIR
 HOUSING REQUIREMENTS, PLEASE REVIEW REQUIREMENT 3 FOR
 USABLE DOORS ARE THE MINIMUM REQUIRED WIDTH. WITH NOT
 HAVING THE INTERIOR DESIGNERS PLANS CODE COMPLIANCE
 CANNOT BE VERIFIED.
 4) SHEET A2.0 NOTES 3,6,12 & 24 DEAL WITH EITHER
 DROPPED CEILINGS AND OR SOFFITS. BOTH OF THESE ELEMENTS
 ARE LOAD BEARING. THE INTERIOR DESIGNER CAN SUBMIT
 DRAWINGS FOR THE CONCEPT BUT THE ARCHITECT OR AN
 FLORIDA P. E. CAN DESIGN THE STRUCTURAL ELEMENTS TO
 MAKE UP THE SOFFITS AND DROPPED CEILINGS. DESIGN
 CRITERIA TO CONSIDER IN THE PLANS ARE THE FOLLOWING:
 ATTACHMENT METHOD TO THE DECK ABOVE, FROM THE FRAMING
 MEMBERS TO FRAMING MEMBERS & FRAMING MEMBERS TO WALL
 ATTACHMENT. NOTE THIS IS HIGH RISE CONSTRUCTION, AND
 NONCOMBUSTIBLE MATERIALS TO BE INSTALLED FBC-B 603.
 PLEASE PROVIDE FRAMING MEMBER SIZE, THICKNESS (GAUGE)
 SPACING BETWEEN FRAMING MEMBERS, THE PSF DESIGNED FOR,
 ALLOWABLE CEILING SPANS AS WELL AS DEFLECTION
 LIMITATION. PROVIDE IF THE FRAMING MEMBERS WILL NEED A
 STIFF BACK AT MID SPAN OR NOT. FBC-B TABLE 2508.1 STEEL
 FRAMING FOR GYPSUM BOARD.
 5) PLEASE NOTE THE ELEVATOR LOBBY WALLS ARE FIRE RATED
 WALLS AND NOTE 24 INDICATES MODIFICATIONS TO THE
 CEILING PLAN. THE ARCHITECT OF RECORD WILL ALSO NEED TO
 PROVIDE THE THROUGH PENETRATION FOR ANY FIRE STOPPING
 ASSEMBLIES REQUIRED FOR PENETRATIONS. 2010 FBC-B
 713.3.1 THROUGH PENETRATIONS.
 6) WITHIN THE PERMIT PACKAGE WAS ALSO SUBMITTED A SALES
 BROCHURE FOR SUPER SAM 125 SOUND INSULATION AND A FLAME
 SPREAD TEST ASTM E 84. THIS IS THE CORRECT TESTING FOR
 FLAME SPREAD BUT NO TESTING REPORTS WERE SUBMITTED FOR
 SOUND. PLEASE PROVIDE COMPLIANCE WITH;
 6A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 6B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 FA THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  