Plan Review Notes
Plan Review Notes For Permit 15050509
Permit Number 15050509
Review Stop P
Sequence Number 1
Notes
Date Text
2015-05-18 12:39:081) PLANS SHOW A WALL MAIN DRAIN BUT THERE IS ALSO A
 MAIN DRAIN DETAIL FOR A FLOOR MAIN DRAIN. CLARIFY.
 2) THE PLAN SHOWS A WALL MAIN DRAIN BUT THE PLAN ALSO
 SHOWS A CHANNEL OUTLET. CLARIFY.
 3) INDICATE ON THE PLAN IF THE POOL HEATER IS NEW OR
 EXISTING. IF NEW, A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE GAS & POOL HEATER.WPB AMEND. TO 2010 FBC SEC.
 105.1.
 4) THE EQUIPMENT SCHEME KEY SHOWS THE MAIN DRAIN AS 2
 1/2 INCHES AND THE PLAN VIEW SHOWS 2 INCHES. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  