2015-06-14 06:05:31 | 1) THE SUBMITTED PLANS SHOW THE EXISTING SPACE BEING |
| CONVERTED INTO TWO SEPARATE UNITS. INDICATE THE TYPE OF |
| OCUPANCY OF THE SPACES PER THE 2010 FBC SEC.303. |
| ADDITIONAL PLUMBING FIXTURES MAY BE REQUIRED PER TABLE |
| 403.1 OF 2010 FBC-PLUMBING. |
| 2) INDICATE THE SQUARE FOOTAGE AND OCCUPANT LOAD OF |
| BOTH SPACES ON THE PLANS. 2010 FBC SEC. 107.2.1. |
| 107.3.5.1. |
| 3) ELEVATION # 3 SHOWS THE WATER CLOSET LOCATED AT |
| 1'-8" FROM THE REAR WALL TO THE CENTERLINE OF THE WATER |
| CLOSET. COMPLY W/ 2010 FBC-ACCESSIBILITY CODE |
| SEC.604.2. |
| 4) THE INSTALLATION OF THE REAR GRAB BAR SHALL COMPLY |
| WITH 2010 FBC SEC.604.5.2. |
| 5) THE LOCATION OF THE TOILET PAPER DISPENSER SHALL |
| COMPLY WITH FAC SEC. 604.7. |
| 6) THE HEIGHT OF THE GRAB BARS SHALL BE INSTALLED IN |
| ACCORDANCE WITH 2010 FAC SEC.609.4. THE HEIGHT SHALL BE |
| MEASURED TO THE TOP OF THE GRIPPING SURFACE. |
| 7) SHOW THE CLEAR FLOOR SPACE FOR THE WATER CLOSET AND |
| LAVATORY ON THE FLOOR PLAN. CLEAR FLOOR SPACES SHALL |
| COMPLY WITH 2010 FAC SEC.604.3 & SEC.305.3. |
| 8) DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| ANY FIXTURE PER FAC SEC. 603.2.3.( SEE EXCEPTIONS) |
| 9) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE |
| CHANGES BEING MADE TO THE PLUMBING SYSTEM. WPB AMEND. |
| TO 2010 FBC SEC. 107.2.1. |
| |