Plan Review Notes
Plan Review Notes For Permit 15050499
Permit Number 15050499
Review Stop M
Sequence Number 1
Notes
Date Text
2015-06-23 07:48:351ST REVIEW: FBC 2010 MECHANICAL
  
 1) THE PLAN INDICATES TWO NEW TENANT SPACES ARE BEING
 CREATED FROM ONE, HOWEVER MINIMAL DETAILS HAVE BEEN
 PROVIDED FOR COMFORT CONDITIONING. PLEASE PROVIDE THE
 FOLLOWING LIST OF REQUIRED INFORMATION, PLAN DETAILS
 AND SPECIFICATIONS FOR EACH NEW OCCUPANCY:
 A) MIINIMUM VENTILATION CALCULATIONS PER TABLE 403.3
 FBC MECHANICAL. INDICATE THE REQUIRED AND PROVIDED
 OUTSIDE AIR CFM'S.
 B) AC LOAD CALCULATIONS PER ACCA MANUAL N, OR
 ASHRAE/ACCA STANDARD 183- SECTION 503.2.1 FBC-10 ENERGY
 CONSERVATION.
 C) ENERGY CALCULATIONS: SUBMIT EITHER COMPLIANCE FORMS
 502 OR 506- TABLE 101.4.1 FBC-10 ENERGY.
 D) AC LAYOUT PLANS: SHOW THE NEW SUPPLY AND RETURN DUCT
 RUNS INCLUDING DUCT SIZES AND CFM DISTRIBUTION,
 LOCATIONS OF EQUIPMENT, REFRIGERANT AND CONDENSATE
 PIPING RUNS AND DETAILS.
 E) AC EQUIPMENT SCHEDULES- MAKES AND MODELS OF AC
 EQUIPMENT, COOLING AND HEATING CAPACITIES, EFFICIENCY
 RATINGS, ELECTRICAL DATA.
 F) AIR DISTRIBUTION SCHEDULE-TYPE OF DUCTWORK,
 DIFFUSERS, AND GRILLS,
 G) AC EQUIPMENT INSTALLATION AND DUCT HANGING AND
 SUPPORT DETAILS.
 2) PROVIDE TOILET ROOM EXHAUST DETAILS- EXHAUST FAN
 EQUIPMENT SCHEDULES, EXHAUST DUCT TYPES AND SIZES AND
 EXHAUST DUCT RUNS AND TERMINATION LOCATIONS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  