Plan Review Notes
Plan Review Notes For Permit 15050499
Permit Number 15050499
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-05-27 14:31:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE OCCUPANY IS NOT CLEARLY INDICATED;
 STORE/COMMERCIAL IS GENERAL AND VAGUE. PLEASE PROVIDE
 EXISTING AND PROPOSED OCCUPANCY PER NFPA 101.
  
 2) A LIFE SAFETY PALN IS NOT PROVIDED. COMPLETE LIFE
 SAFETY PLANS FOR EACH OCCUPANCY SHALL BE PROVIDED THAT
 ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON
 PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS,
 EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 3) THE FIRE WALL DOES NOT INDICATE A FIRE RATING. A 2HR
 FIRE RATING IS REQUIRED WITH FIRE WALL DETAIL DRAWINGS,
 INCLUDING LISTED SEALED OPENINGS.
  
 4) NO DIMENSIONS ARE INDICATED. PLEASE INDICATED ALL
 DIMENSIONS ON THE RESUBMITTAL.
  
 5) EXIT DOOR HARDWARE IS NOT INDICATED. DOORS SHALL BE
 ARRANGED TO BE OPENED READILY FROM THE EGRESS SIDE
 WHENEVER THE BUILDING IS OCCUPIED. LOCKS, IF PROVIDED,
 SHALL NOT REQUIRE THE USE OF A KEY, TOOL, OR SPECIAL
 KNOWLEDGE OR EFFORT FOR OPERATION FROM THE EGRESS SIDE.
  
 INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS
 PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  
 THUMB-TURN LOCK WHEN EQUIPPED ON OTHER DOORS IS SHALL
 BE INSTALED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW
 (SUCH AS ADAMS RITE 4089 OR SIMILAR).
  