Plan Review Notes
Plan Review Notes For Permit 15050499
Permit Number 15050499
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-09 13:43:2315050499
 3234 S. DIXIE HWY
 COMMERCIAL REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 ON THE PANEL SCHEDULE INCLUDE THE SHOW WINDOW LIGHTING
 AND SIGN CIRCUIT. PROVIDE SHOW WINDOW LIGHTING OUTLETS.
 NEC 210.62, 408.4, 600.5
  
 PROVIDE LIGHTING CONTROLS FOR ENERGY CONSERVATION SO
 THAT THE INTERIOR AND EXTERIOR LIGHTING CONTROLS
 PROVIDED FUNCTION IN ACCORDANCE WITH THE FLORIDA ENERGY
 CODE. EXTERIOR AUTOMATIC CONTROLS SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. VERIFY THE
 LIGHTING AND SIGN TIME CLOCKS HAVE BATTERY BACKUP. FBC
 ENERGY CONSERVATION 505.2
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 PROVIDE SPECIFICATIONS/DETAIL FOR FIRESTOPPING THE
 RECEPTACLES ON THE NEW FIREWALL SEPERATION. NEC 300.21
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  