2015-06-24 11:42:14 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15050499 |
| ADD: 3234 S. DIXIE HWY. |
| L. B. ROWE |
| TEL: (561)635-8227 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JUNE 24/2015 |
| ACTION: DENIED |
| |
| 1) SHEET A1 DOES NOT INDICATE UNDER THE 2010 EXISTING |
| BUILDING CODE TO WHAT COMPLIANCE METHOD THE PLANS WERE |
| DESIGNED/ |
| |
| 2) THE PLANS DO NOT INDICATE IF THE BUILDING IS FIRE |
| SPRINKLERED OR NOT. 107.3.5.1.1 MINIMUM COMMERCIAL |
| BUILDING PLAN REVIEW CRITERIA. |
| |
| 3) THE PLANS INDICATE SPLITTING ONE TENANT SPACE AND |
| CREATING TWO TENANT SPACES. THE PLANS DO NOT PROVIDE |
| WHAT DESIGN THE TENANT SEPARATION WALL WILL BE DESIGNED |
| TOO? 2010 FBC-B 709.1.6. PLEASE PROVIDE DETAIL OF THE |
| TENANT SEPARATION WALL. |
| |
| 4) SHEET A1 INDICATES THERE IS TO BE REPLACEMENT |
| WINDOWS AND DOORS. PLEASE PROVIDE THE WIND DESIGN |
| CRITERIA FOR THIS LOCATION. |
| WIND DESIGN CRITERIA |
| 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| NEGATIVE TABLE 1609.2(2) . |
| |
| 5) PLEASE PROVIDE THE MISSING PRODUCT APPROVALS TO |
| COMPLY WITH: 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) STOREFRONTS |
| |
| 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 7) PLEASE NOTE IF THIS IS A NON-SPRINKLERED BUILDING |
| THE COMMON PATH OF TRAVEL IS 75 FEET FOR BUSINESS AND |
| MERCANTILE OCCUPANCIES. |
| 2010 FBC-B 1014.3. THE TENANCY IN 3234 DOES NOT HAVE A |
| REAR DOOR MAKING THE TRAVEL DISTANCE OVER 75 FEET. THIS |
| WILL REQUIRE A SECOND MEANS OF EGRESS TO COMPLY WITH |
| FBC-B 1014.3. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |