Plan Review Notes For Permit 15050486 |
Permit Number |
15050486 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-08-10 12:16:45 | PLUMBING APPROVED WITH PROVISO: | | THESE ITEMS SHALL BE CORRECTED PRIOR TO THE FIRST | | INSPECTION. | | | | 1) SHT.P-1 IS LISTED AS GROUND FLOOR PLUMBING BUT THE | | PLAN IS PLUMBING NOTES. WHAT HAPPENED TO THE GROUND | | FLOOR PLUMBING PLAN? SUBMIT A GROUND FLOOR PLUMBING | | PLAN FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. | | 2) THE STORM RISER SHOWS A 3" LINE DRAINING INTO A | | SMALLER 2" LINE. THIS VIOLATES THE 2010 FBC-PLUMBING | | SEC.706.3 AND 1101.6.A LARGER DRAIN LINE CANNOT DRAIN | | INTO A SMALLER DRAIN LINE. | | 3) SCUPPERS SHALL NOT HAVE AN OPENING DIMENSION LESS | | THAN 4 INCHES. THE PLAN SHOWS THE SCUPPER WITH A 2 INCH | | OPENING. COMPLY WITH 2010 FPC SEC. 1107.3. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | |
|