Plan Review Notes
Plan Review Notes For Permit 15050486
Permit Number 15050486
Review Stop P
Sequence Number 2
Notes
Date Text
2015-08-10 12:16:45PLUMBING APPROVED WITH PROVISO:
 THESE ITEMS SHALL BE CORRECTED PRIOR TO THE FIRST
 INSPECTION.
  
 1) SHT.P-1 IS LISTED AS GROUND FLOOR PLUMBING BUT THE
 PLAN IS PLUMBING NOTES. WHAT HAPPENED TO THE GROUND
 FLOOR PLUMBING PLAN? SUBMIT A GROUND FLOOR PLUMBING
 PLAN FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE STORM RISER SHOWS A 3" LINE DRAINING INTO A
 SMALLER 2" LINE. THIS VIOLATES THE 2010 FBC-PLUMBING
 SEC.706.3 AND 1101.6.A LARGER DRAIN LINE CANNOT DRAIN
 INTO A SMALLER DRAIN LINE.
 3) SCUPPERS SHALL NOT HAVE AN OPENING DIMENSION LESS
 THAN 4 INCHES. THE PLAN SHOWS THE SCUPPER WITH A 2 INCH
 OPENING. COMPLY WITH 2010 FPC SEC. 1107.3.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR