Plan Review Notes For Permit 15050486 |
Permit Number |
15050486 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-08-05 12:46:42 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- REVISE ENERGY CALCULATIONS SUBMITTED. A) CONDITIONED | | FLOOR AREA ON ITEM #6 DOESN'T MATCH PLANS. B) NEED | | INSULATION BETWEEN GARAGE & 2ND FLOOR. C) REVISE WINDOW | | OVERHANG DEPTH TO MATCH PLANS. GABLE END WALLS DON'T | | PROVIDE 8" OVERHANG DEPTH. | | 2- PROVIDE COMPLETE HANDRAIL AND GUARDRAILS (INTERIOR | | AND EXTERIOR) DETAILS/SPECIFICATIONS SHOWING COMPLIANCE | | WITH THE LIVE LOADS OF TABLE R301.5. | | 3- SHEET A2.3: FLAT ROOF NEEDS OVERFLOW SCUPPERS. SEC. | | R903.4.1 | | 4- REVISE LOCATION OF ATTIC ACCESS LOCATED IN CLOSET | | 202B. NEED HEADROOM. ACCESS IS BLOCKED BY THE CLOTHES | | ROD. SEC. R807. | | 5- THE PROJECT INFORMATION ON THE SOIL TEST REPORT | | SUBMITTED DOESN'T MATCH PROPOSED CONSTRUCTION. REVISE | | AS REQUIRED. | | 6- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R1 | | SUBMITTED: PERIMETER & CORNER AREAS WAS SELECTED BASED | | ON EXPOSURE "B". THIS DOESN'T MATCH PLANS. SEE SHEET | | S000. REVISE AS REQUIRED. |
|