Plan Review Notes
Plan Review Notes For Permit 15050486
Permit Number 15050486
Review Stop B
Sequence Number 2
Notes
Date Text
2015-08-05 12:46:42BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE ENERGY CALCULATIONS SUBMITTED. A) CONDITIONED
 FLOOR AREA ON ITEM #6 DOESN'T MATCH PLANS. B) NEED
 INSULATION BETWEEN GARAGE & 2ND FLOOR. C) REVISE WINDOW
 OVERHANG DEPTH TO MATCH PLANS. GABLE END WALLS DON'T
 PROVIDE 8" OVERHANG DEPTH.
 2- PROVIDE COMPLETE HANDRAIL AND GUARDRAILS (INTERIOR
 AND EXTERIOR) DETAILS/SPECIFICATIONS SHOWING COMPLIANCE
 WITH THE LIVE LOADS OF TABLE R301.5.
 3- SHEET A2.3: FLAT ROOF NEEDS OVERFLOW SCUPPERS. SEC.
 R903.4.1
 4- REVISE LOCATION OF ATTIC ACCESS LOCATED IN CLOSET
 202B. NEED HEADROOM. ACCESS IS BLOCKED BY THE CLOTHES
 ROD. SEC. R807.
 5- THE PROJECT INFORMATION ON THE SOIL TEST REPORT
 SUBMITTED DOESN'T MATCH PROPOSED CONSTRUCTION. REVISE
 AS REQUIRED.
 6- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R1
 SUBMITTED: PERIMETER & CORNER AREAS WAS SELECTED BASED
 ON EXPOSURE "B". THIS DOESN'T MATCH PLANS. SEE SHEET
 S000. REVISE AS REQUIRED.