2015-06-25 09:27:521ST REVIEW: FBC 2010 MECHANICAL
  
 1) PROVIDE AC LOAD CALCULATIONS FOR THE AC SYSTEMS IN
 ACCORDANCE WITH ACCA MANUAL J- SECTION 403.6.1 FBC-10
 ENERGY CONSERVATION.
 2) THE SUBMITTED ENERGY CALCULATION FORM 405-10 IS
 INCOMPLETE: A) DOCUMENT MUST BE SIGNED AND DATED BY THE
 PREPARER AND THE OWNER- SEE PAGE 1. B) CODE COMPLIANCE
 CHECKLIST ON PAGE 6 MUST BE CHECKED OFF. C) THE INPUT
 DATA REPORT INDICATING THE THERMAL ENVELOPE
 CONSTRUCTION AND INSULATION MATERIALS AND VALUES MUST
 BE SUBMITTED. PLEASE NOTE THE PLAN DOES NOT CLEARLY
 INDICATE INDICATE WALL, CEILING, AND ATTIC INSULATIONS
 AND R-VALUES TO CORRELATE WITH THE CALCS- REFERENCE
 SECTION 103.22. FBC-10 ENERGY CONSERVATION.
 3) SHEET M-1, AIR HANDLER CLOSET: A) PROVIDE THE
 DIMENSIONS OF THE RETURN AIR GRILL D1400 AT CLOSET. B)
 PROVIDE THE DIMENSIONS OF THE AIR HANDLER CLOSET AND
 AIR HANDLER CLEARANCE MEASUREMENTS IN COMPLIANCE WITH
 SECTION M1305.1.1 FBC-10 RESIDENTIAL. C) INDICATE THE
 THE TYPE OF AIR BARRIER TO BE INSTALLED ON THE WALLS
 AND CEILING OF THE CLOSET AND HOW IT WILL BE SEALED. D)
 PROVIDE DETAILS FOR THE DOUBLE DOORS- PLEASE NOTE RATED
 DOORS WITH THRESHOLD AND WEATHER STRIPPING ARE
 REQUIRED- SECTIONS R302.5.1 & M1601.4.1
 4) M-2 AIR HANDLER CLOSET: A) REFERENCE COMMENTS 3B, &
 C ABOVE, AND ALSO INDICATE THE DIMENSIONS OF THE RETURN
 DUCT AND GRILL MAKING CONNECTION INTO THE CLOSET
 5) M-3: PLEASE REMOVE THE DUCT SMOKE DETECTOR NOTES
 FROM THE CONTROLS DIAGRAM UNLESS THEY ARE ACTUALLY
 BEING INSTALLED- NOTE THEY ARE NOT REQUIRED FOR SINGLE
 FAMILY HOMES.
  