Plan Review Notes
Plan Review Notes For Permit 15050486
Permit Number 15050486
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-25 13:13:52PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED. AS THIS WAS A PAGE BY PAGE
 REVIEW, YOU WILL NOTICE REPEATED COMMENTS ON EACH
 RESPECTIVE PAGE. EACH OF THE COMMENTS NOTED HAVE BEEN
 CLOUDED OR IN SOME WAY IDENTIFIED IN A RED LAYER ON THE
 DIGITAL PLANS.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 SHEET E-0
 1. AMEND THIS NOTE TO ALSO INCLUDE: THE TIP OF A
 CEILING (PADDLE) FAN BLADE, PER NFPA 29.8.3.4(8)
 2. CORRECT THIS TO READ: NFPA 101, 2012 EDITION
 3. CORRECT THIS TO READ: NFPA 72, 2010 EDITION
 4. THOUGH THE INDIVIDUAL PANEL CALCS WILL COMPLY WITH
 THE PROPOSED CONDUCTORS AND THE SERVICE CONDUCTORS AS A
 WHOLE. THE NUMBERS AS REFLECTED HEREIN SHALL BE
 CORRECTED.
 SHEET E-1
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL
 2. AN ADDITIONAL OUTLET WILL BE REQUIRED IN THIS AREA
 TO COMPLY WITH MINIMUM OUTLET SPACING REQUIREMENTS
 3. THESE OUTLETS CAN'T BE BEHIND OR OBSTRUCTED BY THE
 POOL EQUIPMENT.
 4. AN ADDITIONAL OUTLET WILL BE REQUIRED IN THIS AREA
 TO COMPLY WITH MINIMUM OUTLET SPACING REQUIREMENTS
 5. PER NFPA 29.8.3.4(9), A SMOKE DETECTOR IS REQUIRED
 IN THIS AREA
 6. ACCORDING TO THE CIRCUIT SCHEDULE OF PANEL "A",
 CIRCUIT 23 IS FOR THE REFRIGERATOR. INDICATE IF AN
 ADDITIONAL CIRCUIT WILL BE DRAWN FOR THE MICROWAVE.
 7. CORRECT THIS MISQUOTED CODE SECTION. THE APPLICABLE
 FBC IS 2010 SECTION 907.2.11.4
 8. THE FOLLOWING NOTES WERE ADDED TO THE DRAWING:
 A) NEC 240.24 LOCATION IN OR ON PREMISES. (A) & (B)
 PANELS SHALL BE LOCATED SUCH THAT OVER CURRENT DEVICES
 ARE ACCESSIBLE AND THAT OCCUPANTS SHALL HAVE ACCESS TO
 OCP DEVICES.
 B) NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 C) NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 D) NEC 406.8(B) RECEPTACLES IN WET LOCATIONS. 15- AND
 20-AMPERE, 125- AND 250-VOLT RECEPTACLES INSTALLED IN A
 WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS
 WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS
 INSERTED. ALL 15- AND 20-AMPERE, 125- AND 250-VOLT
 NONLOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE.
 SHEET E-2
 1. PER NFPA 29.8.3.4(9), A SMOKE DETECTOR IS REQUIRED
 IN THIS AREA & PER FBC-R 315 IT SHALL BE COMBINATION
 SMOKE & CARBON MONOXIDE DETECTOR.
 2. NEC 210.52(E)(3) BALCONIES. BALCONIES GREATER THAN
 20 SQ. FT. SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE BALCONY.
 3. THIS DETECTOR ALONE DOES NOT MEET THE LOCATION
 REQUIREMENTS OF NFPA 29.5.1(2) WITH RELATION TO BEDROOM
 3 OR THE FUTURE BONUS ROOM.
 4. THIS AHU SHALL HAVE A DISCONNECT AS REQUIRED BY NEC
 440.14
 5. REARRANGE THE BEDROOM OUTLETS TO COMPLY WITH NEC
 210.52
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
  