2015-07-07 09:07:26 | NEW SINGLE FAMILY RESIDENCE, BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- PLANS ARE MISSING THE DOORS AND WINDOWS SCHEDULE. |
| PRODUCT APPROVALS SUBMITTED WILL BE REVIEWED WHEN THE |
| DOORS AND WINDOWS SCHEDULES ARE PROVIDED. SEC. R301 OF |
| 2010 FBC. |
| ALSO, EGRESS WILL BE REVIEWED WHEN COMPLETE INFORMATION |
| IS SUBMITTED. |
| |
| 2-PROVIDE PRODUCT APPROVAL AS REQUIRED BY F.A.C. |
| 61G20-3 FOR: |
| A) ENTRY DOOR AS SHOWN ON PLANS. INFORMATION SUBMITTED |
| DOESN'T HAVE A FLORIDA PRODUCT APPROVAL NUMBER OR |
| MIAMI-DADE NOA NUMBER. IF THERE IS NO AN APPROVED |
| ASSEMBLY, THEN MANUFACTURER MAY SUBMIT COMPLETE |
| ENGINEERING FOR BUILDING OFFICIAL APPROVAL. |
| |
| B) THERMA TRU DOOR PRODUCT APPROVAL FL 7630-R4 |
| SUBMITTED DOESN'T MEET THE DESIGN PRESSURES CALCULATED |
| BY THE ENGINEER OF RECORD. NEED PRODUCT APPROVAL THAT |
| MEETS THE CALCULATED DESIGN PRESSURES. |
| |
| C) FLAT ROOF ASSEMBLY. AND, CLEARLY IDENTIFY APPROVED |
| ASSEMBLY TO BE INSTALLED. AND, PROVIDE SIGNED AND |
| SEALED RAS 117 CALCULATIONS IF REQUIRED TO MEET THE |
| DESIGN PRESSURES OF SEC. R301. |
| |
| D) BALCONY WATERPROOFING UNDERLAYMENT THAT IS DESIGNED |
| TO RECEIVE TILE AS SHOWN ON PLANS. AND, PROVIDE SIGNED |
| AND SEALED RAS 117 CALCULATIONS IF REQUIRED TO MEET THE |
| DESIGN PRESSURES OF SEC. R301. ALSO, PROVIDE PRODUCT |
| APPROVAL FOR MATERIAL SPECIFIED FOR BALCONY ABOVE ENTRY |
| AREA (WITH RAS 117 CALCULATIONS, IF REQUIRED). |
| |
| E) BAHAMA SHUTTERS AS SHOWN ON SHEET A3.1. AND, PROVIDE |
| COMPLETE INSTALLATION SCHEDULE. |
| |
| F) GARAGE DOOR AS SHOWN ON SHEET A3.1 |
| |
| G) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| NOTE: PRODUCT APPROVALS SUBMITTED HAVE A |
| DRAWINGS/SUBMITTAL REVIEW STAMP. THIS STAMP IS NOT |
| ACCEPTABLE. IT DOESN'T IDENTIFY THE FIRM OR THE DESIGN |
| PROFESSIONAL REVIEWING THE PRODUCT APPROVALS. |
| |
| 4- 5V-CRIMP ROOF PANEL NOA 11-0810.10 SUBMITTED: |
| CLEARLY IDENTIFY WHICH SYSTEM IS GOING TO BE USED TO |
| VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| R301 OF 2010 FBC-RESIDENTIAL. |
| |
| 5- WINDOW MULLIONS: CLEARLY IDENTIFY ALL MULLION SIZES |
| TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| |
| 6- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| R401.3 OF 2010 FBC-RESIDENTIAL. |
| |
| 7- REVISE ENERGY CALCULATIONS SUBMITTED. SEC. |
| 103.2.1.1.2 AND SEC. 103.2.2 OF 2010 FBC-ENERGY |
| CONSERVATION. |
| ***NOTE: INFORMATION ON ENERGY CALCULATIONS AND PLANS |
| NEED TO BE COORDINATED TO AVOID UNNECCESARY DELAYS AND |
| CONFLICTS. |
| |
| A) COMPLETE INFORMATION ON TOP OF FORM: OWNER, CORRECT |
| BUILDER'S NAME, PERMIT OFFICE AND JURISDICTION NUMBER. |
| |
| B) CONDITIONED FLOOR AREA ON ITEM #6 DOESN'T MATCH |
| PLANS. NOTE: ALSO TAKE INTO CONSIDERATION THE BONUS |
| ROOM ON SECOND FLOOR. SEE MECHANICAL PLAN. |
| |
| C) NEED INSULATION ON EXTERIOR WALLS, ADJACENT WALLS. |
| SEC. 401.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| D) NEED INSULATION ON CEILING. CLARIFY WHERE ARE THE |
| CATHEDRAL/SINGLE ASSEMBLY CEILINGS. SEC. 401.2 OF 2010 |
| FBC-ENERGY CONSERVATION. |
| |
| E) NEED INSULATION BETWEEN A/C SPACES AND NON-A/C |
| SPACES. SEC. 401.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| F) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC. |
| 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| G) REVISE TYPE OF ROOF ON PAGE 2 OF 6 TO MATCH PLANS. |
| |
| H) CLARIFY WHERE ARE THE WOOD DOORS SHOWN ON PAGE 3 OF |
| 6. |
| |
| I) REVISE WINDOW OVERHANG DEPTH AND SEPARATION TO MATCH |
| PLANS. |
| |
| ***NOTE: LABELS WILL BE REQUIRED FOR INSPECTION FOR THE |
| WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR SPECIFIED ON |
| ITEM #7. |
| |
| 8- ELEVATIONS SHOWN ON THE A1.1 SITE PLAN DON'T MATCH |
| THE ELEVATIONS SHOWN ON THE SURVEY. REVISE AS REQUIRED |
| TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 9- SHEET A2.1: |
| A) SPECIFY POWDER ROOM DOOR SIZE TO SHOW COMPLIANCE |
| WITH SEC. R320. |
| |
| B) PROVIDE SPECIFICATIONS OF GARAGE DOOR LEADING TO |
| MAIN HOUSE TO SHOW COMPLIANCE WITH SEC. R302.5.1 |
| |
| 10- SET OF PLANS IS MISSING DRAWING A7.1 LISTED IN THE |
| LIST OF DRAWINGS ON SHEET A1.1. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 11- PROVIDE COMPLETE HANDRAIL AND GUARDRAILS (INTERIOR |
| AND EXTERIOR) DETAILS AND SPECIFICATIONS SHOWING |
| COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5 AND ALL |
| THE REQUIREMENTS OF SEC. R311.7.7 AND R312. |
| |
| 12- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| STAIRWAY SHOWING COMPLIANCE WITH SEC. R311.7. |
| |
| 13- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION OF EXTERIOR CEILINGS AT LOGGIA AND ENTRY |
| PORCH. SEC R301. |
| |
| 14- SHEET A2.2: CLARIFY WHAT'S THE DOTTED SQUARE SHOWN |
| IN THE CENTER OF THE STAIRWAY. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 15- SHEET A2.3: |
| A) FLAT ROOF NEED MAIN ROOF DRAINS AND AND OVERFLOW |
| SCUPPERS TO COMPLY WITH SEC. R903.4 AND R903.4.1 |
| |
| B) REVISE ROOF DRAIN DETAIL. CLARIFY IF INSTALLING ROOF |
| RIGID INSULATION. COORDINATE WITH BUILDING WALL |
| SECTIONS, THE ENERGY CALCULATIONS AND FLAT ROOF PRODUCT |
| APPROVAL APPROVED ASSEMBLY. SEC. 103.2.2 OF 2010 |
| FBC-ENERGY CONSERVATION. |
| |
| C) COORDINATE ROOF MEMBRANE AND FLAT ROOF NOTES WITH |
| PRODUCT APPROVALS SUBMITTED TO AVOID CONFLICTS. SEE |
| APPROVED ASSEMBLIES AND REVISE INFORMATION AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 16- GUTTERS WITH DOWNSPOUTS ARE REQUIRED FOR EAVES LESS |
| THAN 6". PROVIDE COMPLETE DETAILS AND SPECIFICATIONS. |
| PROVIDE DIMENSIONS FOR ALL EAVES. SEC. R318.6 |
| |
| 17- SPECIFY WINDOW SILL HEIGHT ON ALL SECOND FLOOR |
| WINDOWS TO VERIFY COMPLIANCE WITH SEC. R612.2 |
| |
| 18- LABELING ORIENTATION OF EAST AND WEST ELEVATIONS |
| ARE INCORRECT.. EAST ELEVATION IS WEST ELEVATION AND |
| WEST ELEVATION IS EAST ELEVATION. REVISE AS REQUIRED TO |
| MATCH ACTUAL BUILDING ORIENTATION. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 19- PROVIDE FRAMING DETAILS FOR ARCHED ENTRY DOOR. SEC. |
| R301. |
| |
| 20- PROVIDE ICC EVALUATION REPORT FOR THE SPECIFIED |
| ICYNENE INSULATION (PLEASE MAKE SURE IS THE CURRENT |
| REPORT). SEC. R316. |
| |
| 21- PROVIDE SPECIFICATIONS FOR CEILING ABOVE GARAGE. |
| TABLE R302.6. |
| |
| 22- SPECIFY ATTIC ACCESS LOCATION AND SIZE. SEC. R807. |
| |
| 23- COORDINATE FASTENING OF WINDOW STRUCTURAL BUCKS |
| SHOWN ON SHEET A5.2 WITH FASTENING SHOWN ON DETAIL 08 |
| OF SHEET S400. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 24- SHEET S000: (1) CLARIFY WHY THERE IS NOT ROOF ZONE |
| #3 ON MASTER BEDROOM BALCONY. (2) CLARIFY WHY FLAT ROOF |
| ON SECOND FLOOR IS ZONE 1. SEC. R301. |
| |
| 25- PROVIDE COPY OF SOIL TEST REPORT REFERENCED ON THE |
| NOTES OF THE FOOTING SCHEDULE. SEC. R401.4. |
| |
| 26- NOA 06-0222.01 SPECIFIED FOR PRECAST LINTELS ON |
| SHEET S400 IS EXPIRED. NEED CURRENT NOA. COORDINATE |
| WITH NOA SUBMITTED. |
| |
| *** PLEASE PROVIDE REPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| *** REPLACE ANY REVISED DRAWING TO EXPEDITE THE REVIEW |
| PROCESS. |
| |