2015-06-13 04:03:46 | 1) THE CREATION OF THE NEW UNIT TO A GYM IS INCLUDING | | THE EXISTING TOILET ROOMS THAT WERE PREVIOUSLY LOCATED | | IN THE ADJACENT ATTORNEY'S OFFICE. AFTER LOOKING AT THE | | BUILDOUT PLANS FOR THE ATTORNEY'S OFFICE FROM 2008, IT | | APPEARS THE ATTORNEY'S OFFICE WILL BE DEFICIENT IN THE | | MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES PER THE | | 2010 FPC TABLE 403.1.THE INCLUSION OF THE EXISTING | | TOILET ROOMS WILL CAUSE THE NON-CONFORMITY OF THE | | ADJACENT TENANT SPACE.REFER TO WPB AMENDMENTS TO 2010 | | FBC SEC.102.6. | | 2) SUBMIT AN ENLARGED PLAN OF THE ACCESSIBLE SHOWER AND | | SHOW THE CLEAR INSIDE DIMENSIONS OF THE SHOWER. COMPLY | | WITH 2010 FBC-ACCESSIBILITY SEC.608. | | 3) SHT.P-1 - ELEVATIONS - THE MEASUREMENTS SHOWN ON THE | | DETAILS ARE SO SMALL THEY ARE ILLEGIBLE. SUBMIT CLEAR | | AND LEGIBLE DETAILS FOR REVIEW PER WPB AMEND. TO 2010 | | FBC SEC. 107.2.1. | | 4) SUBMIT 2 COPIES OF MANUF. SPECIFICATION SHEETS FOR | | THE AQUATIC ADA SHOWER COMPARTMENT. AT A MINIMUM, | | PREFAB UNITS SHALL COMPLY WITH 2010 FPC SEC.417.1. | | | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|