Plan Review Notes For Permit 15050482 |
Permit Number |
15050482 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-15 14:48:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) PROVIDE DIMENSIONS TO ALL WALLS. | | | | 2) PROVIDE AN ENTIRE BUILDING LAYOUT, NOT JUST THIS | | SPACE, ON THE SITE PLAN. | | | | 3) PROVIDE A COMPLETE LIFE SAFETY PLAN THAT ILLUSTRATES | | OCCUPANT LOAD, TRAVEL DISTANCES, COMMON PATHS OF | | TRAVEL, EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING | | TO A PUBLIC WAY, FIRE EXTINGUISHER LOCAIONS. | | | | 4) PROVIDE A DOOR SCHEDULE THAT INCLUDES LATCH HARDWARE | | AND LOCKING MECHANISMS. BASED ON OCCUPANCY LOAD PANIC | | HARDWARE MAY BE REQUIRED. | | | | 5) THE FIRE RESISTIVE RATING OF THE SEPARATION WALLS | | SHALL COMPLY WITH THE MINIMUM RATING REQUIREMENTS OF | | THE FLORIDA BUILDING CODE AND THE OCCUPANCIES THAT ARE | | SEPARATED. PROVIDE ADJACENT OCCUPANCY CLASSIFICATIONS | | AND REQUIRED SEPARATIONR FIRE RATING PER EXACT SECTION | | OF THE FLORIDA BUILDING CODE. |
|