Plan Review Notes For Permit 15050482 |
Permit Number |
15050482 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-07 15:44:44 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | THE CORRECTIONS NOTED. | | | | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | RESUBMITTED FOR A SECOND REVIEW: | | 1. CORRECT THE ELECTRICAL RISER DIAGRAM TO SHOW THE | | ELECTRIC METER AHEAD OF THE MAIN DISCONNECT. | | 2. INDICATE PROPER GROUNDING FOR THE SERVICE ON THE | | RISER DIAGRAM. | | 3. PER FBC-B EMERGENCY LIGHTING IS REQUIRED IN THE | | BATHROOMS | | 4. NEC 600.5 REQUIRES A DEDICATED 20 AMP CIRCUIT FOR | | SIGNAGE IN AN ACCESSIBLE LOCATION CLOSE TO EACH | | ENTRANCE. (THE OVERHEAD DOOR DOES NOT COUNT). | | 5. ADDITIONAL EMERGENCY LIGHTS MAY BE REQUIRED. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU | | |
|