Plan Review Notes
Plan Review Notes For Permit 15050482
Permit Number 15050482
Review Stop E
Sequence Number 1
Notes
Date Text
2015-07-07 15:44:44PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
 1. CORRECT THE ELECTRICAL RISER DIAGRAM TO SHOW THE
 ELECTRIC METER AHEAD OF THE MAIN DISCONNECT.
 2. INDICATE PROPER GROUNDING FOR THE SERVICE ON THE
 RISER DIAGRAM.
 3. PER FBC-B EMERGENCY LIGHTING IS REQUIRED IN THE
 BATHROOMS
 4. NEC 600.5 REQUIRES A DEDICATED 20 AMP CIRCUIT FOR
 SIGNAGE IN AN ACCESSIBLE LOCATION CLOSE TO EACH
 ENTRANCE. (THE OVERHEAD DOOR DOES NOT COUNT).
 5. ADDITIONAL EMERGENCY LIGHTS MAY BE REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  