2015-05-16 14:23:59 | 5/16/2015 |
| PROJECT: 133 MURRAY RD SERVICE CHANGE |
| PERMIT#:15050449 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1STELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) PROVIDE A PANEL SCHEDULE FOR EACH PANEL INDICATING |
| THE OCPD AND WIRE SIZE FOR EACH CIRCUIT. NEC 408.4 |
| |
| 2) INDICATE ON THE RISER DIAGRAM THE CONDUIT AND WIRE |
| SIZE FOR THE SERVICE ENTRANCE AND FOR EACH OF THE |
| SUB-FEEDS. |
| |
| 3) INDICATE THE SIZE OF THE FEED THROUGH BRANCH WIRING |
| NIPPLE FROM PANEL "A" AND INDICATE WHAT IS ON THE BACK |
| SIDE OF PANEL "A" TO RECEIVE THE BRANCH WIRING LEAVING |
| PANEL "A" THROUGH THIS NEW NIPPLE. |
| |
| 4) REVISE THE SERVICE ENTRANCE CONDUCTORS TO EACH OF |
| THE MAIN BREAKERS PANELS. THE RISER DIAGRAM INDICATES |
| THE USE OF 2/0CU TO EACH MAIN. IF THERE WERE ONLY ONE |
| MAIN YOU COULD UTILIZE NEC 310.15(B)(6) WHICH WOULD |
| ALLOW THE USE OF 2/0CU. HOWEVER, THERE ARE TWO MAINS. |
| THEREFORE THIS ARTICLE DOES NOT APPLY AND YOU NEED TO |
| USE NEC 310.16 TO SIZE YOUR SERVICE ENTRANCE AND |
| FEEDERS. |
| |
| 5) INDICATE ON THE RISER DIAGRAM THE INSTALLATION OF A |
| GROUNDING ELECTRODE SYSTEM IN COMPLIANCE WITH THE NEC |
| 250.50, 250.52, 250.66, AND 250.94 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |