2015-07-24 14:45:16 | RESIDENTIAL (R3) RENOVATIONS, MECHANICAL REVIEW |
| COMMENTS. |
| CODE: 2010 FBC |
| |
| 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2 |
| COPIES) AS REQUIRED BY SEC. M1401.3 OF 2010 |
| FBC-RESIDENTIAL |
| |
| 2- EQUIPMENT LISTED ON THE MECHANICAL PLAN TO MATCH |
| EQUIPMENT LISTED ON THE EQUIPMENT SIZING CALCULATIONS |
| REQUIRED ON ITEM #1 ABOVE. SEC. 107.3.5.3(10) CITY |
| AMENDMENTS. |
| |
| 3- INFORMATION SHOWN ON THE AIR COOLED CONDENSING UNIT |
| SLAB MOUNTED DETAIL IS NOT LEGIBLE. REVISE AS REQUIRED. |
| SEC. 107.2.1.4 CITY AMENDMENTS. |
| |
| 4- THE DESIGN CRITERIA SPECIFIED ON THE MECHANICAL |
| PLANS IS INCORRECT. ENGINEER OF RECORD TO REVISE AS |
| REQUIRED. SEC. R301 OF 2020 FBC-RESIDENTIAL. |
| |
| 5- TRANSFER GRILLS ON FIRST FLOOR MECHANICAL PLAN ARE |
| LOCATED IN THE DOOR. THE TRANSFER GRILLS NEED TO BE |
| LOCATED ON THE WALL NOT IN THE DOOR A SHOWN ON SECOND |
| FLOOR MECHANICAL PLAN. REVISE AS REQUIRED. SEC. M1602.4 |
| OF THE 200 FBC-RESIDENTIAL. |
| |
| 6- 1ST FLOOR MECHANICAL PLAN: CLARIFY TYPE AND SIZE OF |
| SUPPLY AIR DUCT. IS IT FLEXIBLE OR DUCTED FIBERGLASS. |
| FOR EXAMPLE PLANS SPECIFY 6" DIAMETER SUPPLY BUT IT'S |
| SHOWN AS RECTANGULAR DUCT. SECOND FLOOR IS SHOWN |
| CORRECTLY. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| SUBMIT OLD COPIES FOR REFERENCE. |
| |