2015-07-24 14:45:16RESIDENTIAL (R3) RENOVATIONS, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2
 COPIES) AS REQUIRED BY SEC. M1401.3 OF 2010
 FBC-RESIDENTIAL
  
 2- EQUIPMENT LISTED ON THE MECHANICAL PLAN TO MATCH
 EQUIPMENT LISTED ON THE EQUIPMENT SIZING CALCULATIONS
 REQUIRED ON ITEM #1 ABOVE. SEC. 107.3.5.3(10) CITY
 AMENDMENTS.
  
 3- INFORMATION SHOWN ON THE AIR COOLED CONDENSING UNIT
 SLAB MOUNTED DETAIL IS NOT LEGIBLE. REVISE AS REQUIRED.
 SEC. 107.2.1.4 CITY AMENDMENTS.
  
 4- THE DESIGN CRITERIA SPECIFIED ON THE MECHANICAL
 PLANS IS INCORRECT. ENGINEER OF RECORD TO REVISE AS
 REQUIRED. SEC. R301 OF 2020 FBC-RESIDENTIAL.
  
 5- TRANSFER GRILLS ON FIRST FLOOR MECHANICAL PLAN ARE
 LOCATED IN THE DOOR. THE TRANSFER GRILLS NEED TO BE
 LOCATED ON THE WALL NOT IN THE DOOR A SHOWN ON SECOND
 FLOOR MECHANICAL PLAN. REVISE AS REQUIRED. SEC. M1602.4
 OF THE 200 FBC-RESIDENTIAL.
  
 6- 1ST FLOOR MECHANICAL PLAN: CLARIFY TYPE AND SIZE OF
 SUPPLY AIR DUCT. IS IT FLEXIBLE OR DUCTED FIBERGLASS.
 FOR EXAMPLE PLANS SPECIFY 6" DIAMETER SUPPLY BUT IT'S
 SHOWN AS RECTANGULAR DUCT. SECOND FLOOR IS SHOWN
 CORRECTLY. SEC. 107.2.1 CITY AMENDMENTS.
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT OLD COPIES FOR REFERENCE.
  