2015-07-20 12:53:49 | RESIDENTIAL (R3) RENOVATIONS, BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC |
| |
| 1- ENGINEER OF RECORD TO SIGN AND SEAL BOTH SETS OF |
| DRAWINGS. ONLY ONE WAS SIGNED AND SEALED. CHAPTER 471 |
| F.S. |
| |
| 2- THIS IS NOT ALTERATION LEVEL 2 AS SPECIFIED ON THE |
| PROJECT DATA ON SHEET C-1. THIS IS ALTERATION LEVEL 3. |
| SEC. 405 OF 2010 FBC-EXISTING BUILDING. REVISE AS |
| REQUIRED. |
| |
| 3- SHEET D-1: |
| A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| COMPLIANCE WITH THE FIRE SEPARATION AS REQUIRED BY SEC. |
| 803.2 OF 2010 FBC-EXISTING BUILDING AND SEC. R302.3 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| B) INFORMATION SHOWN ON TENANT SEPARATION FLOOR SECTION |
| DOESN'T MATCH INFORMATION SHOWN ON THE EXISTING TYPICAL |
| WALL SECTION. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 |
| CITY AMENDMENTS. NOTE: LOOK AT THE GA FILE FOR CORRECT |
| INFORMATION FOR THE SELECTED FIRE RATED ASSEMBLY AND |
| REVISE DETAILS ACCORDINGLY. ALSO, TENANT SEPARATION |
| DETAIL IS FOR ONE STORY. THIS IS A TWO STORY HOUSE. |
| REVISE AS REQUIRED TO MATCH ACTUAL CONDITIONS. |
| |
| C) EXISTING TYPICAL WALL SECTION CALLS FOR "EXISTING |
| TILE ROOF". THERE IS NOT TILE ROOF ON THIS HOUSE. |
| REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 4- WINDOW MULLION PRODUCT APPROVAL FL9520-R4 SUBMITTED: |
| A) CLEARLY IDENTIFY SIZE OF MULLIONS TO BE USED TO |
| VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| R301. |
| |
| B) DRAWINGS ARE TOO SMALL. THERE ARE TWO SHEETS OF |
| DRAWINGS INSERTED ON EACH PAGE. PROVIDE ONE SHEET ON |
| EACH PAGE SO DRAWINGS ARE LARGE ENOUGH TO BE READ. SEC. |
| 107.2.1.4 CITY AMENDMENTS. |
| |
| 5- ALL PRODUCT APPROVALS TO BE REVIEWED AND APPROVED IN |
| WRITING (NOT SIGNING AND SEALING) BY THE ENGINEER OF |
| RECORD. SEC. 107.3.4.1 CITY AMENDMENTS. NOT ALL THE |
| PRODUCT APPROVALS SUBMITTED HAVE THE ENGINEER'S REVIEW |
| STAMP. |
| |
| *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| SUBMIT OLD COPIES FOR REFERENCE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |