Plan Review Notes
Plan Review Notes For Permit 15050392
Permit Number 15050392
Review Stop M
Sequence Number 1
Notes
Date Text
2015-06-30 12:59:441ST REVIEW: FBC 2010 RESIDENTIAL
  
 1) PROVIDE A MEANS OF RETURN AIR FROM THE MASTER
 BEDROOM- SECTION M1602.4 FBC-10 RESIDENTIAL.
 2) INDICATE THE DIMENSIONS OF THE RETURN GRILLS IN
 BEDROOMS 2 & 3, AND THE LIBRARY- M1602.4.
 3) INDICATE THE DIMENSIONS OF THE RETURN AIR PLENUM
 DUCTS, AND PLACE A NOTE THAT NO FLEX DUCTS ARE
 PERMITTED TO BE INSTALLED IN THE GARAGE PER SECTION
 R302.5.2.
 4) PROVIDE CONDENSATE DISPOSAL DETAILS- M1411.3 &
 M1411.3.1.
 5) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PADS, AND TIE-DOWN ENGINEERING FOR THE
 CONDENSERS- M1307.2.1.
  