Plan Review Notes For Permit 15050392 |
Permit Number |
15050392 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-30 12:59:44 | 1ST REVIEW: FBC 2010 RESIDENTIAL | | | | 1) PROVIDE A MEANS OF RETURN AIR FROM THE MASTER | | BEDROOM- SECTION M1602.4 FBC-10 RESIDENTIAL. | | 2) INDICATE THE DIMENSIONS OF THE RETURN GRILLS IN | | BEDROOMS 2 & 3, AND THE LIBRARY- M1602.4. | | 3) INDICATE THE DIMENSIONS OF THE RETURN AIR PLENUM | | DUCTS, AND PLACE A NOTE THAT NO FLEX DUCTS ARE | | PERMITTED TO BE INSTALLED IN THE GARAGE PER SECTION | | R302.5.2. | | 4) PROVIDE CONDENSATE DISPOSAL DETAILS- M1411.3 & | | M1411.3.1. | | 5) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE | | CONDENSER PADS, AND TIE-DOWN ENGINEERING FOR THE | | CONDENSERS- M1307.2.1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|