2015-06-27 16:59:53 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| PLANS AND COPY OF PAID RECEIPT. COUNTY IMPACT FEE |
| ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| |
| 2- NEED TO SPECIFY CARBON MONOXIDE ALARMS. SEC R315 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| 3- SHEET A901: REVISE THE SLIDING GLASS DOORS AND |
| WINDOWS HEAD AND JAMB NOTES. BEVELED BUCKS ARE NOT |
| ALLOWED. SEC. R612.10.2 OF 2010 FBC-RESIDENTIAL. |
| |
| 4- SHEET S2: |
| A) DETAIL 1/S2 IS MISSING THE ROOF SHEATHING NAIL TYPE, |
| SIZE AND SPACING. SEC. R803.2.3.1 OF 2010 |
| FBC-RESIDENTIAL. NOTE: COORDINATE WITH ITEM #5 BELOW. |
| |
| B) SPECIFY THE ATTIC LIVE LOAD AS REQUIRED BY TABLE |
| R301.5 OF 2010 FBC-RESIDENTIAL. |
| |
| 5- DETAIL 12/S3: SEC R803.2.3.1 OF 2010 FBC-RESIDENTIAL |
| REQUIRES 8D RING SHANK NAILS MIN. PLYWOOD BLOCKING |
| DETAIL CALLS FOR 10D NAILS. REVISE AS REQUIRED OR |
| PROVIDE CALCULATIONS SHOWING THAT 10D NAILS ARE EQUAL |
| OR BETTER THAN 8D RING SHANK NAILS. SEC. 107.2.1.3 CITY |
| AMENDMENTS. NOTE: COORDINATE WITH ITEM # 4(A) ABOVE. |
| |
| 6- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 7- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST |
| REPORT WITH ALL THE INFORMATION AS REQUIRED BY SEC. |
| 1803.6 FBC-2010. |
| |
| 8- REVISE THE ENERGY CALCULATIONS. SEC 103.2.1.1.2 OF |
| 2010 FBC-ENERGY CONSERVATION: |
| A) PROVIDE CORRECT BUILDER'S NAME, CORRECT PERMIT |
| OFFICE AND CORRECT JURISDICTION NUMBER ON TOP OF FORM. |
| |
| B) IDENTIFY WHERE ARE THE INSULATED DOORS SHOWN ON PAGE |
| 4 OF 6. IT DOESN'T MATCH PLANS AND PRODUCT APPROVALS. |
| |
| C) REVISE THE BUILDING ORIENTATION TO MATCH PLANS. AND, |
| REVISE THE WALLS AND WINDOWS ORIENTATION ACCORDINGLY. |
| |
| D) REVISE THE OVERHANG DEPTH AND SEPARATION OF EACH |
| WINDOW/DOOR TO MATCH PLANS. |
| |
| ***NOTE: WINDOWS AND DOORS LABELS WILL BE REQUIRED |
| SHOWING THE U-FACTOR AND SHGC FACTOR SPECIFIED ON ITEM |
| #7. |
| |
| 9- PROVIDE STRUCTURAL FRAMING DETAIL FOR OVAL WINDOWS |
| AS SHOWN ON PLANS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) MAHOGANY ENTRY DOOR SIZE ASSEMBLY AS SHOWN ON PLANS. |
| |
| B) ROOF TILE. |
| |
| C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL |
| FOR LISTED ADHESIVE. |
| |
| D) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS |
| SPECIFIED ON DETAIL D1 OF SHEET A801. |
| |
| E) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| 11- ENGINEER OF RECORD TO REVIEW AND APPROVE ALL |
| PRODUCT APPROVALS IN WRITING (NOT SIGNING AND SEALING) |
| AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 12- CLARIFY WHY THERE IS ANOTHER ENGINEER (NOT THE |
| ENGINEER OF RECORD) SUBMITTING A "WINDOW & DOOR |
| INSTALLATION?. ALSO, THE DESIGN PRESSURES ARE DIFFERENT |
| THAN THOSE SPECIFIED BY THE ENGINEER OF RECORD. WHICH |
| ONE IS THE ONE WITH THE CORRECT DESIGN PRESSURES? AND, |
| THE SLIDING GLASS DOORS MULLIONS ARE NOT CLEAR |
| (HORIZONTAL OR VERTICAL?). SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 13- CLEARLY IDENTIFY MULLION SIZE FOR OPENINGS #108, |
| #109 AND #110 TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL. CLEARLY |
| IDENTIFY THE VERTICAL AND HORIZONTAL MULLIONS. |
| |
| 14- SLIDING GLASS DOORS NOA 14-0128.11. PAGE 6 OF 22 |
| WAS HIGHLIGHTED WITH TABLE 1A WITH LOWER SILL HEIGHT. |
| DOORS WITH LOW SILL HEIGHT DON'T MEET THE DESIGN |
| PRESSURES FOR OPENING #110. REVISE AS REQUIRED. |
| |
| 15- TRUSS PACKAGE: |
| A) TRUSS PACKAGE DOESN'T COMPLY WITH SEC. 61G15-31.003. |
| THE COVER PAGE IS MISSING THE ENGINEER OF RECORD |
| INFORMATION AND EACH INDIVIDUAL TRUSS DRAWING NEEDS THE |
| TRUSS ENGINEER'S INFORMATION. |
| |
| B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS |
| PACKAGE BEFORE SUBMITTAL. |
| |
| NOTE: TRUSS PACKAGE DOESN'T NEED TO BE RE-SUBMITTED TO |
| THIS OFFICE NOW. ON RESIDENTIAL PROJECTS, THE |
| CONTRACTOR MAY DELIVER THE REVISED TRUSS PACKAGE TO THE |
| INSPECTOR AT TIME OF FRAMING INSPECTION. |
| |
| 16- VALUATION DECLARED IN THE PERMIT APPLICATION IS |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. VALUATION WAS UPDATED TO $568,741. THE |
| PERMIT FEE BALANCE IS $8938.19. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE REVIEW PROCESS. |
| ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| SUBMITT OLD COPY FOR REFERENCE. |
| |