Plan Review Notes
Plan Review Notes For Permit 15050392
Permit Number 15050392
Review Stop B
Sequence Number 1
Notes
Date Text
2015-06-27 16:59:53NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- NEED TO SPECIFY CARBON MONOXIDE ALARMS. SEC R315 OF
 2010 FBC-RESIDENTIAL.
  
 3- SHEET A901: REVISE THE SLIDING GLASS DOORS AND
 WINDOWS HEAD AND JAMB NOTES. BEVELED BUCKS ARE NOT
 ALLOWED. SEC. R612.10.2 OF 2010 FBC-RESIDENTIAL.
  
 4- SHEET S2:
 A) DETAIL 1/S2 IS MISSING THE ROOF SHEATHING NAIL TYPE,
 SIZE AND SPACING. SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL. NOTE: COORDINATE WITH ITEM #5 BELOW.
  
 B) SPECIFY THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 OF 2010 FBC-RESIDENTIAL.
  
 5- DETAIL 12/S3: SEC R803.2.3.1 OF 2010 FBC-RESIDENTIAL
 REQUIRES 8D RING SHANK NAILS MIN. PLYWOOD BLOCKING
 DETAIL CALLS FOR 10D NAILS. REVISE AS REQUIRED OR
 PROVIDE CALCULATIONS SHOWING THAT 10D NAILS ARE EQUAL
 OR BETTER THAN 8D RING SHANK NAILS. SEC. 107.2.1.3 CITY
 AMENDMENTS. NOTE: COORDINATE WITH ITEM # 4(A) ABOVE.
  
 6- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 7- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST
 REPORT WITH ALL THE INFORMATION AS REQUIRED BY SEC.
 1803.6 FBC-2010.
  
 8- REVISE THE ENERGY CALCULATIONS. SEC 103.2.1.1.2 OF
 2010 FBC-ENERGY CONSERVATION:
 A) PROVIDE CORRECT BUILDER'S NAME, CORRECT PERMIT
 OFFICE AND CORRECT JURISDICTION NUMBER ON TOP OF FORM.
  
 B) IDENTIFY WHERE ARE THE INSULATED DOORS SHOWN ON PAGE
 4 OF 6. IT DOESN'T MATCH PLANS AND PRODUCT APPROVALS.
  
 C) REVISE THE BUILDING ORIENTATION TO MATCH PLANS. AND,
 REVISE THE WALLS AND WINDOWS ORIENTATION ACCORDINGLY.
  
 D) REVISE THE OVERHANG DEPTH AND SEPARATION OF EACH
 WINDOW/DOOR TO MATCH PLANS.
  
 ***NOTE: WINDOWS AND DOORS LABELS WILL BE REQUIRED
 SHOWING THE U-FACTOR AND SHGC FACTOR SPECIFIED ON ITEM
 #7.
  
 9- PROVIDE STRUCTURAL FRAMING DETAIL FOR OVAL WINDOWS
 AS SHOWN ON PLANS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) MAHOGANY ENTRY DOOR SIZE ASSEMBLY AS SHOWN ON PLANS.
  
 B) ROOF TILE.
  
 C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVE.
  
 D) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS
 SPECIFIED ON DETAIL D1 OF SHEET A801.
  
 E) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS IN WRITING (NOT SIGNING AND SEALING)
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 12- CLARIFY WHY THERE IS ANOTHER ENGINEER (NOT THE
 ENGINEER OF RECORD) SUBMITTING A "WINDOW & DOOR
 INSTALLATION?. ALSO, THE DESIGN PRESSURES ARE DIFFERENT
 THAN THOSE SPECIFIED BY THE ENGINEER OF RECORD. WHICH
 ONE IS THE ONE WITH THE CORRECT DESIGN PRESSURES? AND,
 THE SLIDING GLASS DOORS MULLIONS ARE NOT CLEAR
 (HORIZONTAL OR VERTICAL?). SEC. 107.2.1 CITY
 AMENDMENTS.
  
 13- CLEARLY IDENTIFY MULLION SIZE FOR OPENINGS #108,
 #109 AND #110 TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL. CLEARLY
 IDENTIFY THE VERTICAL AND HORIZONTAL MULLIONS.
  
 14- SLIDING GLASS DOORS NOA 14-0128.11. PAGE 6 OF 22
 WAS HIGHLIGHTED WITH TABLE 1A WITH LOWER SILL HEIGHT.
 DOORS WITH LOW SILL HEIGHT DON'T MEET THE DESIGN
 PRESSURES FOR OPENING #110. REVISE AS REQUIRED.
  
 15- TRUSS PACKAGE:
 A) TRUSS PACKAGE DOESN'T COMPLY WITH SEC. 61G15-31.003.
 THE COVER PAGE IS MISSING THE ENGINEER OF RECORD
 INFORMATION AND EACH INDIVIDUAL TRUSS DRAWING NEEDS THE
 TRUSS ENGINEER'S INFORMATION.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE BEFORE SUBMITTAL.
  
 NOTE: TRUSS PACKAGE DOESN'T NEED TO BE RE-SUBMITTED TO
 THIS OFFICE NOW. ON RESIDENTIAL PROJECTS, THE
 CONTRACTOR MAY DELIVER THE REVISED TRUSS PACKAGE TO THE
 INSPECTOR AT TIME OF FRAMING INSPECTION.
  
 16- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $568,741. THE
 PERMIT FEE BALANCE IS $8938.19.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMITT OLD COPY FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]