2015-05-19 09:24:31 | 5/19/2015 |
| PROJECT: CLUBHOUSE |
| PERMIT#: 15050303 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: THIS PROJECT IS MUCH MORE INVOLVED THAN JUST |
| THE SIMPLE ELECTRICAL ELEMENTS NOTED IN THIS SCOPE OF |
| WORK SUBMITTED. |
| |
| 1) PROVIDE A GENERAL CONTRACTOR WITH A MASTER PERMIT |
| APPLICATION TO ACCEPT RESPONSIBILTY FOR THE |
| INSTALLATION OF WALLS DOORS AND WINDOWS AS WELL AS ANY |
| ADDITIONAL WORK NOT APPARAENT ON THE PLAN SUBMITTED. |
| |
| 2) PROVIDE SEPARATE M.E.P. CONTRACTORS FOR ALL NEW |
| MECHANICAL, ELECTRICAL, PLUMBING WORK INVOLED. |
| |
| 3) PROVIDE A DESIGN PROFESSIONAL TO CREATE A COMPLETE |
| SET OF DESIGN DOCUMENTS INDICATING ALL ELEMENTS OF THE |
| OVERAL PROJECT. SEE WPB AMENDMENTS TO CHAPTER 107 FOR |
| SUBMITTAL DOCUMENTS REQUIRED. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |