Date |
Text |
2015-05-08 15:48:01 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PROVIDE TWO (2) SETS OF AN EVALUATION REPORT FROM A | | CERTIFIED ROOFING CONSULTANT OF THE EXISTING ROOF | | SYSTEM'S ABILITY TO RESIST PROJECT DESIGN PRESSURES AND | | FOR COMPATIBILITY AND BOND PERFORMANCE WITH THE | | SELECTED ADHESIVE AS DOCUMENTED THROUGH FIELD UPLIFT | | TESTING IN ACCORDANCE WITH ASTM E907, FM LPDS 1-52 OR | | ANSI/SPRI IA-1. SEE NOTE 12 ON PAGE 2 OF 39. |
|