2015-06-08 11:09:27 | 6/8/2015 |
| PROJECT: KITCHEN REMODEL |
| PERMIT#: 15050180 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| FEE(S). |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) NEC 210.52(A) |
| VERIFY RECEPTACLE SPACING. THERE APPEAR TO BE WALLS IN |
| NEED OF RECEPTACLES TO MEET THIS MINIMUM REQUIREMENT. |
| SEE THE DINING ROOM WALLS SPECIFICALLY. |
| |
| 2) NEC 210.7 (B) |
| THE PANEL SCHEDULE INDICATES CIRCUITS 5 AND 7 ARE FOR |
| THE DISHWASHER AND DISPOSAL BUT INDICATE A SINGLE |
| RECEPTACLE FEEDING BOTH. WHERE TWO OR MORE BRANCH |
| CIRCUITS SUPPLY DEVICES OR EQUIPMENT ON THE SAME YOKE, |
| A MEANS TO SIMULTANEOUSLY DISCONNECT THE UNGROUNDED |
| CONDUCTORS SUPPLYING THOSE DEVICES SHALL BE PROVIDED AT |
| THE POINT AT WHICH THE BRANCH CIRCUITS ORIGINATE. |
| |
| 3) NEC 422.31 |
| A DISCONNECT IS REQUIRED FOR THE WATER HEATER. |
| |
| 4) FBC-RESIDENTIAL 314 AND 315. |
| SMOKE DETECTORS ARE REQUIRED TO BE INSTALLED INSIDE AND |
| OUTSIDE OF SLEEPING AREAS. WHEN ALTERATIONS, REPAIRS, |
| OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR |
| MORE SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING |
| DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE |
| EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW |
| DWELLINGS. |
| |
| 5) NEC 210.12, 406.11 |
| ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT AND AFCI PROTECTED. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |